Prepared For:
Michael Bishop
Property Address:
10621 N. 103 Ave.
Phoenix, AZ. 85040
![]() |
![]() |
| Date: 10/19/2005 | Time: 10:11 AM | Report ID: Michael Bishop |
| Property: 10621 N. 103 Ave. Phoenix, AZ. 85040 |
Customer: Michael Bishop |
Real Estate Professional: One Year Warranty |
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor or qualified professional. All costs associated with further inspection fees and/or repair or replace of items, components or units should be considered.
Inspected: This term means I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing normal wear and tear. The notation does not mean that the item is perfect but does meet a reasonable standard on the day of inspection.
Repair or Replace: The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Requires Immediate Attention: The item, component or unit needs immediate attention by a qualified professional or contractor for the safety and/or health of the occupants of the building or further major deterioration or failure of a system or component. Worsen appreciably, cause damage, or be a serious hazard.
Unsafe: A condition in a readily accessible, installed system or component which is judged to be a significant risk of personal injury during normal day to day use. The risk may be due to damage, deterioration, improper installation or a change in adopted construction standards.
Not Tested: I did inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not testing or operating.
You have contracted with us to perform a general
inspection in accordance with Arizona industry standards for the inspection
profession. This is different from our technically exhaustive inspection which
takes several days to complete, involves the use of specialized instruments, the
dismantling of equipment, video scanning, destructive testing and laboratory
analysis. Our purpose is to identify defects or adverse conditions that need
additional evaluation, are safety concerns or may lead to costs that would
significantly affect your evaluation of the property at the time of this
inspection.
THIS HOME IS LESS THEN ONE YEAR OLD. THE BUILDER IS RESPONSIBLE FOR THE REPAIRS WHICH ARE NECESSARY IN A TIMELY MANNER.
| Client Is
Present: Yes |
Age Of Building: New Construction |
Building Faces: North |
| Weather: Clear |
Temperature: Over 90 degrees |
Rain in last 3
days: No |
| 1.0 | BUILDING
CHARACTERISTICS Comments: Inspected The home being inspected is eleven months old, therefore the builder is responsible for repairs associated with the construction of the residence since there is a warranty in place. There are numerous flaws in the construction of this home associated with the application of materials, and methods used. The home was occupied at the time of this inspection, but nevertheless we make every attempt possible to evaluate the entire home. |
| 1.1 | GENERAL EXTERIOR SITE
DRAINAGE Comments: Repair or Replace The right side front of the home needs the landscape rock and soil lowered so there is a minimum of six inches of clearance, from the bottom of the stucco to grade, with a slope away from the home. There should be a gradual swale from the front of the block fence to the road, so rain water is able to drain correctly from the back yard. The back yard (right side) needs soil added so rain water is not standing, and is able to freely drain through the holes at the bottom of the block fence. Moisture next to a foundation will have an adverse affect on your home, expansive soil could damage the foundation, and is an invitation for wood destroying insects.
|
| 1.2 | LANDSCAPING NEXT TO
BUILDING Comments: Inspected When you have all the landscaping installed we recommend trees be planted at least 8 feet from your home. Many new homes have small trees planted to close when the home is just completed, and in a few years the branches of the trees begin to cause damage to the home from wind moving the branches against the roof, siding, and fascia of the home. |
| 1.3 | CONCRETE DRIVEWAY, WALKWAYS,
PATIOS, ENTRYWAYS, CONDITION Comments: Repair or Replace The concrete driveway has two significant cracks, in sections of the concrete. The builder is responsible for the exterior concrete surfaces until the warranty expires, the two sections of concrete will need to be replaced. The other walkways and patio concrete surfaces were in acceptable condition, at the time of this inspection.
|
| 1.4 | FENCE AND GATE(S),
CONDITION Comments: Repair or Replace Gate entering rear yard needs auto-closure mechanism adjusted or replaced, we recommend repairing this immediately because there is a pool in the back yard. The state of Arizona requires all gates and doors entering yards where pools are present to have self-closing devices present and operational. |
| 1.5 | IRRIGATION
SYSTEMS Comments: Inspected Operated manually and randomly checking drips/ bubblers/ spray heads (not all were visible). The system functioned properly. Watering devices need occasional inspection by the homeowner for continued proper operation.
|
| 2.0 | FOUNDATION TYPE: THE
STRUCTURAL CONDITION Comments: Inspected The foundation of this home is poured concrete, no concerns were present at the time of inspection. Minor cracks are common in concrete products and the condition of this foundation is considered typical. This is associated with settlement and shrinkage.
|
| 2.1 | FLOOR TYPE: THE VISIBLE
STRUCTURAL CONDITION Comments: Inspected Floors in the home are constructed of poured concrete. The conditions are acceptable with regard to the structural integrity of the concrete slab on grade floor system. There are floor coverings present. There was no visual evidence of a concern such as major wall or ceiling cracks which would tell us that a problem may exist. |
| 2.2 | EXTERIOR AND INTERIOR LOAD
BEARING WALLS: THE STRUCTURAL CONDITION Comments: Inspected Wall structure of home is constructed of wood framing materials. The condition was acceptable with regard to the structural integrity of the wall system. There was no visual evidence of concerns with the framing or methods used in the construction of the home. |
| 2.3 | CEILING MATERIAL: THE
STRUCTURAL CONDITION Comments: Inspected The ceiling structure of the home is constructed with an engineered wood truss system and sheetrock coverings. There were no concerns structurally with the ceilings. |
| 2.4 | ROOF STRUCTURE TYPE: THE
STRUCTURAL CONDITION Comments: Inspected The roof structure of this home is constructed with engineered wood trusses with oriented strand board (OSB) attached to the trusses for roof sheathing. Visually inspecting the condition of the components in the attic, I did not find no concerns present. |
| 2.5 | POSTS, BEAMS, COLUMNS: THE
STRUCTURAL CONDITION Comments: Inspected Stucco covered wood framed columns supporting patio roof structures were in acceptable condition structurally. |
![]() |
![]() |
![]() |
| 3.0 | EXTERIOR WALLS,
CONDITION Comments: Repair or Replace Exterior walls are stucco finish (exterior insulated finish system). The conditions were poor, repairs are needed around the entire perimeter of the home. This is to alert you that there are significant defects in the stucco applied to this home. The west side of the home has the most concerns in which the stucco should be recoated. The cracks on this side of the home are considered excessive by any standards. I would recommend the builder make all repairs in a timely manner. I also strongly recommend the builder warranty the finish for an additional year. There could be a product defect (ingredients) in the stucco which was applied and the finish could continually crack in the future after the builders warranty expires. You may want to have the Arizona Registrar of Contractors document this issue so the builder cannot claim any warranty has expired. The Registrar of Contractors will send a state representative to your residence to perform a courtesy inspection of the stucco and document the time of their inspection so everybody is on the same page should the builder neglect to repair or replace the finish on the home. The Registrar of Contractors have strict guidelines as to the application of stucco on homes or buildings in Arizona and regulates the installation of stucco to current building standards. The stucco must meet or exceed the minimum standards adopted by the American Concrete Institute with regard to the ingredients of the cement based finish, and must be applied in a Professional Workmanlike Manner. There is no tolerance for cracks over 1/16 of an inch and zero tolerance for stucco failing or chipping from window or door frames on a new home. For more information about the Registrar please visit: http://www.rc.state.az.us/
|
| 3.1 | EXTERIOR WALL PAINT (NEW
HOMES) Comments: Repair or Replace I recommend the entire home be repainted after all the stucco is repaired or replaced. There are different colors of paint on the west side of the home and other numerous locations where someone was trying to cover all the excessive cracking in the stucco finish. There is visible mineral/efflorescence penetration from the stucco finish weeping through the paint, which is associated with applying paint before the stucco has cured for the appropriate amount of time. |
| 3.2 | STUCCO WEEP
FLASHING Comments: Repair or Replace The metal weep flashing is not attached to the home properly at the front, to the right of the main entrance door. The flashing is required to be installed tight to the foundation, without excessive gaps. This will allow rain water to deteriorate the framing components, from splashing up under the weep screed. This is also an invitation for wood destroying insects to easily access cellulose products. This needs to be repaired in a timely manner.
|
| 3.3 | WINDOWS AND
FLASHINGS Comments: Repair or Replace Windows are dual pane glass. The conditions were acceptable with regard to their operation and latching. The flashing for windows installed with stucco to the edge of the window frames is not visible but there was no evidence of moisture intrusion around them yet. The stucco is failing at the window frames and also appears it was not installed in a professional like manner, gaps are present between the frames and the wall finish. If the builder chooses not to make the necessary repairs in a timely manner please contact the Arizona Registrar of Contractors: http://www.rc.state.az.us/ Some window glass in the pictures appear to have lost the hermetic seal, this is not the case, it just appears that way in the pictures.
|
| 3.4 | EXTERIOR DOORS AND WEATHER
STRIPPING Comments: Repair or Replace The exterior door from the master bedroom to the rear patio needs the weather stripping adjusted or replaced so sun light cannot be seen from the interior to the exterior and the door closes tightly and evenly.
|
| 3.5 | SOFFITS, FASCIA, EAVES, TRIM,
FLASHINGS Comments: Repair or Replace There are numerous cracks and holes in the stucco finish of the fascia, which need to be repaired in a timely manner before further deterioration continues. I recommend the builder correct this as soon as possible. Rain water has the ability to enter in back of the stucco. Picture #1 is at the rear of the home, above the large upper stationary window in the master bedroom. Picture #2 is on the left side front of the home, the stucco was applied in a less than professional like manner.
|
| 3.6 | EXTERIOR PATIO CEILINGS,
EXTERIOR CEILING FANS Comments: Repair or Replace The sheetrock ceiling needs to be caulked and repainted where it meets the wall framing at all edges. This is considered normal from shrinkage, but needs to be repaired. |
| 3.7 | EXTERIOR ELECTRICAL OUTLETS,
GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected Exterior outlets are Ground fault circuit interrupters. All exterior outlet circuits were tested by manually tripping the ground faults. The exterior light fixtures operated correctly, and were attached to the building properly at the time of this inspection. |
| 3.8 | EXTERIOR PLUMBING,
FAUCETS Comments: Inspected Hose faucets are present at front and rear of home. They operated properly at the time of inspection. There are anti-siphon devices on the faucets. |
| 4.0 | HOME ROOF
COVERINGS Comments: Repair or Replace Roof covering was observed at numerous areas with a ladder because walking cement roofing material can cause breakage. Tiles which are cracked/broken and dislodged are present. This roof has a 30 lb. composition asphalt underlayment applied to the roof sheathing before the installation of the tiles. Generally in time the underlayment becomes deteriorated and water will begin leaking into the home, especially when this concern is directly related to the metal roof flashing also. Repairing the tiles in a timely manner would be needed. The area which needs repair is represented in picture #4. I recommend the roofing contractor review the rest of the roof which was not accessible from a ladder and make any repairs which are necessary.
|
| 4.1 | ROOF FLASHINGS, DRIP EDGE
FLASHING Comments: Repair or Replace The stucco needs to be repaired at the metal flashing where the wire and foam insulation are visible. Picture #2 is the location which needs the repair made.
|
| 4.2 | ROOF PENETRATIONS, PLUMBING
VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, CONDITION, AND PROPER
SEALING Comments: Inspected The metal flashing around the roof penetrations such as plumbing vents appeared acceptable. There was no sign of any moisture penetration around them in the attic, which would tell us they are not sealed or installed correctly. |
| 5.0 | ATTIC ACCESS Comments: Inspected Attic access was gained with a ladder at the hallway ceiling. The access is for heating and cooling professionals to perform maintenance on the equipment in the attic.
|
| 5.1 | INSULATION AND VAPOR
RETARDERS, TYPE VISIBLE Comments: Repair or Replace Blown Cellulose insulation is about four to five inches thick at areas: Under the R-30 resistance value which is supposed to be installed at the area to the left of the access opening to the attic. Picture #1 represents a measurement of Four inches. I recommend the insulation contractor install the correct amount which is clearly stapled to the wall "R-30 Value", which is clearly not present, and is a current building requirement. The lack of insulation is causing the cooling equipment to operate more than necessary, increasing your electrical consumption.
|
| 5.2 | VENTILATION Comments: Repair or Replace The level of ventilation should be improved. Generally recommended that (1) square foot of free vent area be provided for every (150) square ft. of living space. Proper ventilation will help keep the home cooler in hot weather. Gable vents would greatly increase the ventilation of the attic area and would be recommended. The city building inspector could have allowed the construction of the home in this fashion. Other homes in the neighborhood built by the same builder have gable vents, the builder and city inspector could have overlooked the installation. I would ask the builder about this before your warranty expires. |
| 5.3 | ROOF UNDERLAYMENT, FRAMING,
VISIBLE Comments: Inspected Roof framing was inspected while in the attic. There was no altered structural components present. The roof sheathing does not have any moisture stains present. |
| 5.4 | EXPOSED ATTIC WIRING
CONDITIONS Comments: Inspected The electrical wiring which is visible and not covered with insulation was correctly installed. Wires are generally located throughout the attic area of a building under the insulation. When modifications have been made they are sometimes visible. We report when the wiring methods are not consistent with the current electrical code. |
| 6.0 | MAIN WATER SHUTOFF DEVICE,
LOCATION Comments: Inspected The water shut-off valve to turn off all water to the home is located at the front of the home, the exterior plumbing is copper. We do not operate these valves. Operation could cause the valve to break or leak from not being operated often. These valves accumulate calcium deposits inside and generally will not operate correctly after years of not using the valve. We recommend turning the brass valve off at the meter box located behind the curb if a situation should occur where the need to turn the entire water supply off to the home is needed, and call a plumber.
|
| 6.1 | INTERIOR WATER SUPPLY
MATERIAL, DISTRIBUTION SYSTEM, AND SUPPORTS Comments: Inspected Interior water supply piping is Copper and PEX polyethylene plastic. There was no concern with the water supply piping. |
| 6.2 | INTERIOR DRAIN, WASTE AND
VENT PIPE MATERIAL Comments: Inspected Interior drains and the drainage vent pipes are constructed of ABS and PVC plastic piping. |
| 6.3 | HOT WATER HEATER(S) AND
SYSTEM Comments: Inspected Hot water heater is natural gas manufactured by A.O.Smith in 2004 with a capacity of 50 gallons located in the garage. Plumbing, venting and gas connections are consistent with current building standards. I recommend a carbon monoxide detector be installed in the garage for this gas appliance.
|
| 6.4 | GAS METER AND
SHUTOFF Comments: Inspected The natural gas entering the home can be turned off at the valve pictured at the meter in case of an emergency.
|
| 6.5 | SEWER
CLEANOUTS Comments: Inspected The sewer cleanouts are accessible in the front of the home. |
There are a wide variety of electrical systems, and which any one particular system may not conform to current standards or provide the same degree of service or safety. The most significant concern about a system is the fact that the NEC, National Electrical Code is not retroactive, and therefore many residential systems do not comply with the current standards. However in the interest of safety, we regard every electrical deficiency and recommended upgrade as a latent hazard that should be repaired as soon as possible by a licensed electrician before the close of escrow, because an electrician could recommend additional upgrades. We recommend upgrading outlets to Ground Fault Circuit Interrupters (GFCI's) which are a relatively inexpensive but essential safety feature and have been around for approximately 30 years and have been required in specific locations. Exterior outlets and pools were the first GFCI requirement in all residential dwellings in 1971, and the list has grew ever since, bathrooms in 1975, garages in 1978, spas and hot tubs in 1981, kitchens and basements in 1987, wet bars in 1993, and all kitchen countertop receptacles with exception of the refrigerator in 1996. Similarly, AFCI, arc fault circuit interrupters the very latest in circuit breaker technology and have been required in all bedroom receptacles since 2002, if your home does not have them we will recommend them because there are thousands of arc fault fires each year, another simple inexpensive upgrade every home should have.
![]() |
![]() |
| 7.0 | MAIN ELECTRICAL METER AND
DISTRIBUTION PANEL LOCATION Comments: Inspected Main electrical service meter and distribution panel are located at the right side front of the home. |
| 7.1 | MAIN ELECTRICAL PANEL AND
DISTRIBUTION PANEL CONDITION Comments: Inspected The electrical equipment was installed in a professional like manner. The meter panel and distribution equipment are correctly attached to the wall of the home. The panels are weather protected, the distribution cover is labeled correctly, identifying what circuit breaker controls the circuit it is connected to. |
| 7.2 | MAIN SERVICE ENTRANCE
CONDUCTOR TYPE AND THE AMPERAGE AND VOLTAGE Comments: Inspected The main underground electrical service conductors are not visible because of the configuration of this type electrical equipment and meter box. The electrical service providers conductors are terminated in the meter box and have steel bars used as conductors from the meter to the Hot Bus of the distribution panel. The equipment was labeled inspected and passed by the service provider before the safety shield was installed. |
| 7.3 | MAIN OVERLOAD DEVICE AND THE
ELECTRICAL SYSTEM GROUNDING Comments: Inspected The main overload device to turn All electrical power off to the entire home is a 200 Amp. single throw circuit breaker. A copper grounding conductor for this electrical system is visible in main service panel, correctly installed and terminated to the foundation. The exact termination point is not visible because the conductor is installed inside the wall cavity. Grounding was tested for this electrical system at the panel and interior of the building. The main electrical service equipment was inspected for conditions which may exist that could jeopardize the safety of the occupants of this home. All visible wiring connections, panel weather protection, and the general overall condition was inspected. I found no concerns present which would need repairs or corrections made by a licensed electrician. |
| 7.4 | BRANCH CIRCUIT WIRE TYPE AND
CIRCUIT BREAKERS Comments: Inspected Branch circuit wires are copper 120 Volt and aluminum 240 Volt, single phase. The overload devices are circuit breakers. The branch circuit wires are the correct size connected to the breakers, considered compatible. All circuit wires are installed in a professional like manner. There are Arc Fault Circuit Interrupters connected to bedroom circuit wiring in the distribution panel, these were manually tested in the panel, and functioned as intended. |
HOW A HEAT PUMP WORKS IN THE COOLING
MODE: A Heat Pump is essentially an air conditioner with a few
additions. A Heat Pump has a reversing valve, two metering devices and two
bypass valves. The compressor pumps refrigerant to the reversing valve. The
reversing valve directs the flow of refrigerant to the outside coil (condenser)
where the fan cools and condenses the refrigerant to liquid. The air flowing
across the coil removes heat from the refrigerant. The liquid refrigerant
bypasses the first metering device and flows to the second metering device at
the inside coil (evaporator) and the air becomes cooler. This is the
air that blows into the home. The refrigerant vapor then travels back to
the reversing valve to be directed to the compressor to start the cycle all over
again.
ALL HEATING AND COOLING
EQUIPMENT NEED TO BE SERVICED YEARLY BY A QUALIFIED
PROFESSIONAL.
| 8.0 | AIR CONDITIONING
EQUIPMENT Comments: Inspected The air conditioning system for the home is two Aire-Flo split system electric Heat Pumps. The Air Handlers (blowers, condensers, evaporator coils) are located in the attic. Operating and testing the system in the cooling mode the supply temperature was 60 degrees which is about normal for this type of cooling system. All heating and cooling systems need to be serviced yearly by a qualified professional so they operate efficiently. Refrigerant levels need to be checked and the condenser coils cleaned. A heat pump supplying air even one or two degrees lower after service will greatly reduce your electrical consumption.
|
| 8.1 | REFRIGERANT
LINES Comments: Inspected The refrigerant piping for the Heat Pumps was correctly installed. I did not find any bent or damaged piping where they are visible. They are correctly insulated at the exterior of the home and in the attic. |
| 8.2 | ELECTRICAL
DISCONNECTS Comments: Inspected The electrical disconnects for the Heat Pump(s) were installed correctly at the exterior wall of the home in back of the units. The electrical power can also be turned off at the electrical distribution panel. The disconnect at the unit is for emergencies and service technicians. |
| 8.3 | CONDENSATE DRAIN LINES,
SYSTEM OVERFLOW PAN Comments: Inspected The condensate drainage lines at the Evaporator Coils of the Air Handlers are installed correctly where they are not covered with insulation and visible. The drip pans are properly attached to the bottom of the equipment. |
| 8.4 | HEATING AND AIR HANDLER
EQUIPMENT Comments: Inspected Heating equipment is two Aire-Flo natural gas Forced Air Furnaces located in the attic at the Air Handler(s) of the split system. The outside temperature was not low enough (below 75 degrees) for accurately testing the system in the heating mode. The distribution ducts are located in a hot attic and the system would blow warm air if the furnaces were operating correctly or not. There was a clean blue flame at both furnaces when they were operated, which generally indicates proper operation. We strongly recommend having gas furnaces serviced yearly as normal home maintenance. Inspecting the heating system, all equipment, wiring, supports, and basic condition was acceptable. |
| 8.5 | HEATING EQUIPMENT FLUE AND
VENT PIPES Comments: Inspected The flue vent pipes for the gas furnaces were inspected for correct installation (fastening) and proper termination above the roof. I strongly recommend a carbon monoxide detector be installed in the attic, all homes should have these detectors if there are natural gas appliances present. |
| 8.6 | THERMOSTAT Comments: Inspected The thermostats were manually operated in the cooling and heating mode of the system. |
| 8.7 | DISTRIBUTION DUCTS, PIPING,
SUPPORTS, REGISTERS, FILTERS Comments: Repair or Replace Distribution ducts for the heating and cooling were inspected in the attic. They are insulated flexible type supported with straps as required throughout the attic area. The return air filters are located in the hall ceilings and should be changed monthly. The return register in the main hallway on the left side of the home needs to be fastened to the ceiling correctly and resealed at the edge.
|
| 9.0 | FLOORS Comments: Inspected We report possible visual structural defects of the interior floors. The floor coverings are not part of this inspection, there was no concern present. |
| 9.1 | WALLS,
CEILINGS Comments: Repair or Replace There are sheetrock anomalies in the home which need repair. I recommend you mark all cracks/anomalies with blue painters tape so the contractor can make the repairs which are necessary. These cracks are normal, caused from settlement and shrinkage of the building materials. |
| 9.2 | INTERIOR TRIM,
BASEBOARD Comments: Inspected The interior wood trim and baseboard molding were in good condition at the time of this inspection. |
| 9.3 | INTERIOR
DOORS Comments: Inspected Interior doors were inspected. They operated and latched properly at the time of this inspection. |
| 9.4 | MASTER BEDROOM
CLOSET Comments: Inspected There are minor cracks in the sheetrock, which need to be repaired by the builder. You will need to label the painting anomalies before the builder arrives to make the repairs in the home. The closet shelves are properly attached, the ceiling light fixture operated correctly, and the electrical receptacles are installed properly. |
| 9.5 | CEILING FANS Comments: Inspected Ceiling fans functioned properly when tested. They are properly attached to the ceilings in the various rooms of the house. The dimmer switches for the fan lights operate correctly. |
| 9.6 | ELECTRICAL WIRING, OUTLETS,
SWITCHES, AND LIGHTING Comments: Inspected Receptacles, switches and lighting operate correctly in the living areas. The receptacles were tested for the correct polarity and grounding. There was no concerns found at any receptacle or switch in the home. |
| 9.7 | BEDROOM ARC FAULT CIRCUIT
INTERRUPTER RECEPTACLES Comments: Inspected There are AFCI's, Arc Fault Circuit Interrupters connected to the bedroom wall receptacles. They tripped when manually tested in the distribution panel of the electrical system. Should a receptacle in one of the bedrooms suddenly loose electrical current, a fault may have been sensed by the AFCI, which could be related to a fixture plugged into a receptacle or a faulty AFCI circuit breaker, in any event a electrician should determine the cause. |
| 9.8 | SMOKE
DETECTORS Comments: Inspected Smoke Detectors were tested. They operated manually. We recommend smoke detectors be re-tested periodically, and batteries changed yearly. |
Bathroom fixtures in new homes may need the caulking around tub and shower surrounds resealed, because of shrinkage of the caulk or tile grout. The caulk/sealant and grout appears to be in normal condition now, but if any separation occurs before the builder makes the necessary repairs to your home, labeling any such cracking should be done before the builder arrives to make an assessment of the entire home.
| 10.0 | FLOORS, WALLS,
CEILINGS Comments: Inspected The bathrooms were in normal condition for a home which has been lived in. There were no concerns present which would need repairs by the contractor, except sheetrock and painting anomalies which in your opinion need repairs.
|
| 10.1 | TUB SHOWER
UNIT(S) Comments: Inspected There were no concerns present at the time of inspection. The fixture operated correctly. |
| 10.2 | SHOWER
UNIT(S) Comments: Inspected The condition was acceptable and the fixture operated correctly. |
| 10.3 | MASTER BATH TUB
UNIT Comments: Inspected This fixture was in acceptable condition, and functioned properly at the time of inspection. |
| 10.4 | BATHROOM SINKS, COUNTERTOPS,
CABINETS Comments: Inspected The sinks and cabinets are in acceptable condition in the bathrooms. The water and drainage pipes are connected to current plumbing standards. |
| 10.5 | SINK DRAINAGE
PIPES Comments: Inspected There were no active leaks at the time of this inspection. |
| 10.6 | TOILETS Comments: Inspected The toilets are correctly installed, no visible leaks present and flushed properly. |
| 10.7 | BATHROOM, ELECTRICAL OUTLETS,
GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected Ground fault circuit interrupters were tested in all bathrooms, no concerns were present. The lighting functioned properly. |
| 10.8 | BATHROOM , WATER PRESSURE,
AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected The water pressure in the bathrooms was acceptable. The drains emptied correctly. |
| 10.9 | BATHROOM EXHAUST
VENTILATION Comments: Inspected Bathroom ventilation fans were functional in the bathroom ceilings. |
| 10.10 | BATHROOM
WINDOWS Comments: Inspected The windows were functional and properly installed. |
| 11.0 | FLOOR, WALLS,
CEILINGS Comments: Inspected The condition of the kitchen was normal for a home which was lived in. We report damage to areas which would need a contractor to repair, not normal wear and tear.
|
| 11.1 | KITCHEN CABINETS AND
COUNTERTOPS Comments: Inspected Cabinets and countertops are in acceptable condition. |
| 11.2 | KITCHEN SINK AND
FAUCET Comments: Inspected The faucet operated correctly. The sink was in acceptable condition. |
| 11.3 | WATER PRESSURE AND DRAINAGE
FUNCTIONAL FLOW Comments: Inspected The water pressure was acceptable and drains emptied correctly. |
| 11.4 | SINK DRAINAGE
PIPES Comments: Inspected There were no active leaks at the time of this inspection. |
| 11.5 | KITCHEN ELECTRICAL OUTLETS,
GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected Ground fault circuit interrupters were tested. Lighting functioned correctly. |
| 11.6 | FOOD DISPOSER Comments: Inspected Disposer functioned properly. Electrical and plumbing connections were consistent with current standards. |
| 11.7 | DISHWASHER Comments: Inspected The dishwasher was not operated, the electrical and plumbing connections are consistent with current standards. |
| 12.0 | FLOOR, WALLS,
CEILING Comments: Inspected The room is in acceptable condition. |
| 12.1 | DOOR Comments: Inspected The door from the laundry room to the kitchen functioned as intended. |
| 12.2 | LAUNDRY PLUMBING
CONNECTIONS Comments: Not Tested Plumbing connections are consistent with current standards. The washer was connected to the faucets, there was no visible leaks at the time of this inspection. |
| 12.3 | DRYER POWER
SUPPLY Comments: Inspected The power supply to operate a dryer is 240 Volt electricity. There is a natural gas line also available for a clothes dryer, above the baseboard molding to the right of the dryer. This line has a cap on it correctly installed, with no gas leaking, this was tested. |
| 12.4 | ELECTRICAL OUTLETS, GROUND
FAULT CIRCUITS, LIGHTING Comments: Inspected Ground fault circuit interrupters were functional, and manually tested, the lighting operated as intended. |
| 12.5 | DRYER VENTING Comments: Inspected The dryer vent pipe is installed through the roof (from interior wall). I recommend having the metal pipes cleaned as normal home maintenance yearly. Dryer debris generally collects at the base of the vent pipe connection. |
| 12.6 | ROOM EXHAUST
VENTILATION Comments: Inspected Laundry room has an exterior vented fan. This operated properly when inspected. There is a rain cap installed where the vent pipes terminate above the roof line. |
| 12.7 | SINK OR WASH
BASIN Comments: Inspected The sink operated correctly. There was no active leaks in the drainage or water supply lines. |
| 13.0 | FLOORS, WALLS,
CEILINGS Comments: Repair or Replace The ceiling has excessive cracking and anomalies present. We recommend repairs be made by the builder before your one year warranty expires. This is associated with shrinkage of the material, which happen frequently in garage areas because they are not conditioned space.
|
| 13.1 | PASSAGE DOOR TO
INTERIOR/EXTERIOR Comments: Repair or Replace Passage door to interior is fire-rated and self-closing. The bottom threshold for the door to the exterior is separating from the concrete slab, this needs to be fastened correctly and resealed. The exterior wood trim is separating from the door casing and needs to be fastened correctly.
|
| 13.2 | GARAGE DOOR MATERIAL AND
CONDITION Comments: Inspected Garage door is metal, condition was acceptable. |
| 13.3 | GARAGE DOOR
OPENER(s) Comments: Inspected Auto-Opener functioned properly when met with resistance (reversed), electric eyes are present and operational. The door track for the opener is fastened to wood framing correctly, no concerns were present. |
| 13.4 | ELECTRICAL OUTLETS,
LIGHTING Comments: Inspected Ground fault circuit interrupters functioned correctly, they were manually tripped and reset, the lighting and switches were operational. |
| 13.5 | GARAGE DOOR
TRIM Comments: Inspected The vinyl and wood trim around the garage door was installed correctly. |
![]() Phoenix Home Inspectors, Inc. 10599 E. Betony Dr. Scottsdale AZ.
85255 | |
|
Customer | |
|
Property Address | |
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the building.
This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
| 1.1 | GENERAL EXTERIOR SITE DRAINAGE | |
| Repair or Replace | ||
|
The right side front of the home needs
the landscape rock and soil lowered so there is a minimum of six inches of
clearance, from the bottom of the stucco to grade, with a slope away from
the home. There should be a gradual swale from the front of the block
fence to the road, so rain water is able to drain correctly from the back
yard. The back yard (right side) needs soil added so rain water is not
standing, and is able to freely drain through the holes at the bottom of
the block fence. Moisture next to a foundation will have an adverse affect
on your home, expansive soil could damage the foundation, and is an
invitation for wood destroying insects. | ||
| 1.3 | CONCRETE DRIVEWAY, WALKWAYS, PATIOS, ENTRYWAYS, CONDITION | |
| Repair or Replace | ||
|
The concrete driveway has two significant
cracks, in sections of the concrete. The builder is responsible for the
exterior concrete surfaces until the warranty expires, the two sections of
concrete will need to be replaced. The other walkways and patio concrete
surfaces were in acceptable condition, at the time of this
inspection. | ||
| 1.4 | FENCE AND GATE(S), CONDITION | |
| Repair or Replace | ||
|
Gate entering rear yard needs auto-closure
mechanism adjusted or replaced, we recommend repairing this immediately
because there is a pool in the back yard. The state of Arizona requires
all gates and doors entering yards where pools are present to have
self-closing devices present and
operational. | ||
| 3.0 | EXTERIOR WALLS, CONDITION | |
| Repair or Replace | ||
|
Exterior walls are stucco finish (exterior
insulated finish system). The conditions were poor, repairs are needed
around the entire perimeter of the home. This is to alert you that there
are significant defects in the stucco applied to this home. The west side
of the home has the most concerns in which the stucco should be recoated.
The cracks on this side of the home are considered excessive by any
standards. I would recommend the builder make all repairs in
a timely manner. I also strongly recommend the builder warranty the
finish for an additional year. There could be a product defect
(ingredients) in the stucco which was applied and the finish could
continually crack in the future after the builders warranty expires. You
may want to have the Arizona Registrar of Contractors document this issue
so the builder cannot claim any warranty has expired. The Registrar of
Contractors will send a state representative to your residence to perform
a courtesy inspection of the stucco and document the time of their
inspection so everybody is on the same page should the builder neglect to
repair or replace the finish on the home. The Registrar of Contractors
have strict guidelines as to the application of stucco on homes or
buildings in Arizona and regulates the installation of stucco to current
building standards. The stucco must meet or exceed the minimum standards
adopted by the American Concrete Institute with regard to the ingredients
of the cement based finish, and must be applied in a Professional
Workmanlike Manner. There is no tolerance for cracks over 1/16 of an inch
and zero tolerance for stucco failing or chipping from window or door
frames on a new home. For more information about the Registrar please
visit: http://www.rc.state.az.us/ | ||
| 3.1 | EXTERIOR WALL PAINT (NEW HOMES) | |
| Repair or Replace | ||
|
I recommend the entire home be repainted after
all the stucco is repaired or replaced. There are different colors of
paint on the west side of the home and other numerous locations
where someone was trying to cover all the excessive cracking in the stucco
finish. There is visible mineral/efflorescence penetration from the stucco
finish weeping through the paint, which is associated with applying paint
before the stucco has cured for the appropriate amount of
time. | ||
| 3.2 | STUCCO WEEP FLASHING | |
| Repair or Replace | ||
|
The metal weep flashing is not attached to the
home properly at the front, to the right of the main entrance door. The
flashing is required to be installed tight to the foundation, without
excessive gaps. This will allow rain water to deteriorate the framing
components, from splashing up under the weep screed. This is also an
invitation for wood destroying insects to easily access cellulose
products. This needs to be repaired in a timely manner. | ||
| 3.3 | WINDOWS AND FLASHINGS | |
| Repair or Replace | ||
|
Windows are dual pane glass. The conditions
were acceptable with regard to their operation and latching. The flashing
for windows installed with stucco to the edge of the window frames is not
visible but there was no evidence of moisture intrusion around them
yet. The stucco is failing at the window frames and also appears it was not installed in a professional like manner, gaps are present between the frames and the wall finish. If the builder chooses not to make the necessary repairs in a timely manner please contact the Arizona Registrar of Contractors: http://www.rc.state.az.us/ Some window glass in the pictures appear to have lost the hermetic seal, this is not the case, it just appears that way in the pictures. | ||
| 3.4 | EXTERIOR DOORS AND WEATHER STRIPPING | |
| Repair or Replace | ||
|
The exterior door from the master bedroom to
the rear patio needs the weather stripping adjusted or replaced so sun
light cannot be seen from the interior to the exterior and the door closes
tightly and evenly. | ||
| 3.5 | SOFFITS, FASCIA, EAVES, TRIM, FLASHINGS | |
| Repair or Replace | ||
|
There are numerous cracks and holes in the
stucco finish of the fascia, which need to be repaired in a timely
manner before further deterioration continues. I recommend the builder
correct this as soon as possible. Rain water has the ability to enter in
back of the stucco. Picture #1 is at the rear of the home, above the large
upper stationary window in the master bedroom. Picture #2 is on the left
side front of the home, the stucco was applied in a less than professional
like manner. | ||
| 3.6 | EXTERIOR PATIO CEILINGS, EXTERIOR CEILING FANS | |
| Repair or Replace | ||
|
The sheetrock ceiling needs to be caulked and
repainted where it meets the wall framing at all edges. This is considered
normal from shrinkage, but needs to be
repaired. | ||
| 4.0 | HOME ROOF COVERINGS | |
| Repair or Replace | ||
|
Roof covering was observed at numerous areas
with a ladder because walking cement roofing material can cause breakage.
Tiles which are cracked/broken and dislodged are present. This roof
has a 30 lb. composition asphalt underlayment applied to the roof
sheathing before the installation of the tiles. Generally in time the
underlayment becomes deteriorated and water will begin leaking into
the home, especially when this concern is directly related to the metal
roof flashing also. Repairing the tiles in a timely manner would be
needed. The area which needs repair is represented in picture #4. I
recommend the roofing contractor review the rest of the roof which was not
accessible from a ladder and make any repairs which are
necessary. | ||
| 4.1 | ROOF FLASHINGS, DRIP EDGE FLASHING | |
| Repair or Replace | ||
|
The stucco needs to be repaired at the metal
flashing where the wire and foam insulation are visible. Picture #2
is the location which needs the repair made. | ||
| 5.1 | INSULATION AND VAPOR RETARDERS, TYPE VISIBLE | |
| Repair or Replace | ||
|
Blown Cellulose insulation is about four
to five inches thick at areas: Under the R-30 resistance value which
is supposed to be installed at the area to the left of the
access opening to the attic. Picture #1 represents a measurement of Four
inches. I recommend the insulation contractor install the correct amount
which is clearly stapled to the wall "R-30 Value", which is clearly not
present, and is a current building requirement. The lack of insulation is
causing the cooling equipment to operate more than necessary, increasing
your electrical consumption. | ||
| 5.2 | VENTILATION | |
| Repair or Replace | ||
|
The level of ventilation should be improved.
Generally recommended that (1) square foot of free vent area be provided
for every (150) square ft. of living space. Proper ventilation will help
keep the home cooler in hot weather. Gable vents would greatly
increase the ventilation of the attic area and would be recommended. The
city building inspector could have allowed the construction of the home in
this fashion. Other homes in the neighborhood built by the same builder
have gable vents, the builder and city inspector could have overlooked the
installation. I would ask the builder about this before your warranty
expires. | ||
| 8.7 | DISTRIBUTION DUCTS, PIPING, SUPPORTS, REGISTERS, FILTERS | |
| Repair or Replace | ||
|
Distribution ducts for the heating and cooling
were inspected in the attic. They are insulated flexible type supported
with straps as required throughout the attic area. The return air
filters are located in the hall ceilings and should be
changed monthly. The return register in the main hallway on the left side
of the home needs to be fastened to the ceiling correctly and resealed at
the edge. | ||
| 9.1 | WALLS, CEILINGS | |
| Repair or Replace | ||
|
There are sheetrock anomalies in the home
which need repair. I recommend you mark all cracks/anomalies with blue
painters tape so the contractor can make the repairs which are necessary.
These cracks are normal, caused from settlement and shrinkage of the
building materials. | ||
| 13.0 | FLOORS, WALLS, CEILINGS | |
| Repair or Replace | ||
|
The ceiling has excessive cracking and
anomalies present. We recommend repairs be made by the builder before your
one year warranty expires. This is associated with shrinkage of the
material, which happen frequently in garage areas because they are not
conditioned space. | ||
| 13.1 | PASSAGE DOOR TO INTERIOR/EXTERIOR | |
| Repair or Replace | ||
|
Passage door to interior is fire-rated and
self-closing. The bottom threshold for the door to the exterior is
separating from the concrete slab, this needs to be fastened correctly and
resealed. The exterior wood trim is separating from the door casing and
needs to be fastened correctly. | ||