| Date: 4/11/2006 | Time: 12:27 PM | Report ID: Gregory Davidson |
| Property: 13799 N. 112th. St. Scottsdale, AZ. 85255 |
Customer: Mr. Gregory Davidson |
Real Estate Professional: Warranty Inspection |
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor or professional.
Inspected: This term means I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing normal wear and tear. The notation does not mean that the item is perfect but does meet a reasonable standard on the day of inspection.
Repair or Replace: The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Requires Immediate Attention: The item, component or unit needs immediate attention by a qualified professional or contractor for the safety or health of the occupants of the building. Could cause further major deterioration, or complete failure of a system or component. Worsen appreciably, cause damage, or be a serious hazard.
Unsafe: A condition in a readily accessible, installed system or component which is judged to be a significant risk of personal injury during normal day to day use. The risk may be due to damage, deterioration, improper installation or a change in adopted construction standards.
Not Tested: I did inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not testing or operating.
IMPORTANT NOTICE TO THIRD PARTIES: Receipt of this report by anyone other than the above listed party(s) is not authorized by Inspect Arizona Companies, Inc. This report is prepared for the sole and exclusive use for the client who signed the INSPECTION AGREEMENT and is subject to the terms and conditions agreed upon. This Inspection Report is a product, and is copyrighted by Inspect Arizona Companies, Inc. at the date of this inspection. Duplication by any means whatsoever is prohibited without prior written permission and authorization from Inspect Arizona Companies, Inc. Unauthorized duplication, use, or reliance of this report shall constitute all parties agreed upon to hold harmless, whether individual, joint or otherwise, Dale Duffy and Inspect Arizona Companies, Inc., their successor's and assignee's.
PERMITS/BUILDING CODE VIOLATIONS: If you are concerned about code violations or building permit information you should: 1) Contract with our company to research permit information available at the appropriate building and safety office, 2) If you have additional concerns with regard to code violations you may contract for a code compliance survey of the property.
You have contracted with us to perform a Builders Warranty inspection in accordance with Arizona industry standards for the inspection profession. This is different from our technically exhaustive inspection which takes several days to complete, involves the use of specialized instruments, the dismantling of equipment, video scanning, destructive testing and laboratory analysis of possible contaminates. Our purpose is to identify defects or adverse conditions that need additional evaluation, are safety concerns or may lead to costs that would significantly affect your evaluation of the property at the time of this inspection. The Arizona minimum Standards for Professional Practice are available online, please click here to view: http://www.btr.state.az.us/az%20Ashi%20Standards.htm
Client Is Present: Yes | Age Of Building: Under 1 Year | Approximate S.F: 2800 |
Weather: Clear | Temperature: Over 65 degrees | Rain in last 3 days: No |
![]() | ![]() |
Inspection Items
|
| 1.0 | BASIC REPORT INFORMATION OR BUILDING CHARACTERISTICS Comments: Inspected | ||
| This inspection report is for the "One Year Builders Warranty",
the inspection report is for repairs which are necessary to be
completed before the warranty expires.
Licensed Builders in Arizona are required by law to provide the buyer with a two year warranty for major defects which need to be made to the house for items that are not functioning as intended, have failed, or were not built consistent with current building standards when the building was constructed. Please read the entire inspection report, there are some major concerns with the exterior stucco finish system, and other items in this report that need to be correct NOW by the builder.
|
| 1.1 | GENERAL EXTERIOR SITE DRAINAGE Comments: Repair or Replace | |||
| On the west (left) side of the house the existing soil is lower at
side of the house and the masonry fence which is allowing water
to stand after a storm.
The Masonry Fence has not been repaired after the drain was installed. Masonry Block companies make "Perforated Blocks" which should be installed at this location in my opinion, rather than the "Black Plastic Drain Cover" (as pictured). All soil grades when the lot is rough graded are required to slope away from the house foundation and toward the street before any landscape rock or grass is installed. The reason for this is water accumulating next to your house foundation, or masonry fence can cause soil to expand if the soil has expansive characteristics. Please read this document regarding Arizona Expansive Soils , this link provides you with additional information about Arizona soils, and why it is important to have the Builder correct the soil grade and (slope) of your lot if expansive soils are present.
|
| 1.2 | TREE OR VEGETATION NEXT TO THE BUILDING Comments: Inspected |
| The condition was acceptable at the time of inspection, but for your
information tree branches and vegetation next to your house can
cause damage.
Wind moving branches will rapidly damage building materials and also allow insect travel. I recommend planting trees a minimum of 8 feet from your home in the future if you decide to plant any. Here is more information about tree root growth next to a house foundation. |
| 1.3 | DRIVEWAY, PARKING LOT, WALKWAYS, PATIOS, ENTRYWAYS, CONDITION Comments: Repair or Replace | ||
| The driveway concrete is higher than the garage floor concrete, this
needs to be repaired by the builder. The garage floor in my
professional opinion should be raised (which is needed anyway
because it is sloped backwards, see garage section of this report).
This link at the Arizona Registrar of Contractors explains your rights as a new home owner if the Builder does not make the necessary repairs in a timely manner. Also visit this link for more information.
|
| 1.4 | FENCE AND GATE(S), CONDITION Comments: Inspected |
| The masonry fence around the property was in normal condition
except what was previously stated regarding the west side drain at
the bottom of the masonry fence.
The metal framed with vertical wood gate at the east side front of the house operated correctly. |
| 1.5 | IRRIGATION SYSTEMS Comments: Inspected |
| I operated the sprinkler-irrigation system manually and inspected
drips, bubblers, and spray heads (not all were visible). The system
functioned properly at the time of this inspection.
The sprinkler-irrigation timer was installed consistent with current building standards, and is fastened to the exterior wall of the house on the east side correctly. Watering devices need occasional inspection by homeowner for continued proper operation. |
| 1.6 | IRRIGATION PIPING Comments: Inspected |
| There was no concern with any irrigation or sprinkler pipes at the
supply source by the main water supply to the house at the right
side front. The pipe is schedule 40 plastic PVC going into the
ground.
While the sprinkler-irrigation system was operating I did not see any leaks today. |
Inspection Items
|
| 2.0 | FOUNDATION TYPE; CONDITION Comments: Inspected |
| The foundation of this House is Post Tension Concrete, no major
concerns were visible at the time of inspection. Minor cracks are
common in concrete products, the condition of this foundation is
considered typical-normal.
The builder is required by the laws of Arizona for the contracting profession to warranty your foundation for two years after you close escrow. |
| 2.1 | FLOOR TYPE; CONDITION Comments: Inspected |
| Floors in the building are constructed of Post Tension (first floor)
and wood framing (second floor).
The conditions are acceptable with regard to the structural integrity of the concrete floor system and the wood framing. There are floor coverings present. There was no visual evidence of a concern such as major wall or ceiling cracks which would tell me that a problem may exist. *Please see the Interior section of this report also regarding the condition of the second floor in the Master Bathroom, walking on the tile I can feel the sub-floor is not attached to the floor framing correctly, which is not a structural concern, but rather an annoyance because of the sound that is heard while walking across it*. |
| 2.2 | EXTERIOR AND INTERIOR LOAD BEARING WALLS; TYPE; CONDITION Comments: Inspected |
| The exterior and interior walls of the house are constructed with
wood framing materials, the walls are covered with sheetrock at the
interior.
There was no visible concern with the wall framing structurally. |
| 2.3 | CEILING MATERIAL; TYPE; CONDITION Comments: Inspected |
| The ceilings in the house are built with wood framing materials and sheetrock. There was no evidence any concern is present structurally. |
| 2.4 | ROOF STRUCTURE TYPE; CONDITION Comments: Inspected |
| The roof structure of this house is constructed with engineered wood
trusses with oriented strand board (OSB) attached to the trusses for
the roof sheathing.
Visually inspecting the condition of the components in the attic, there was no concern where access could be gained. |
| 2.5 | POSTS, BEAMS, COLUMNS TYPE; CONDITION Comments: Inspected |
| Stucco covered wood framed columns are in normal condition
structurally.
*Please see the "Exterior Section" of this report for the condition of the stucco applied to the columns*. |
Inspection Items
|
| 3.0 | EXTERIOR WALLS, CONDITION Comments: Repair or Replace | ||||||||||||||
| The exterior finish applied to this house is Cement Stucco, with styrofoam and lath under the stucco in most locations.
There are numerous concerns around windows and other areas of the Cement Stucco finish where Styrofoam protrudes out from the wall system. These protrusions are known as pop-outs, and are basically built for a design purpose, rather than anything related to the building structurally. But at these pop-outs the Cement Stucco was not applied to current building standards. Stucco is required to be 3/8 thick, with Lath behind the stucco to hold the stucco to the object it is applied to. Inspecting areas around the entire house I found numerous locations the Cement Stucco is falling off already (within 11 months) of the house being finished. There are locations at the front and rear of the house I took pictures of the stucco already missing, and I can push my finger into the stucco without any force what so ever at locations with approximately less than 1/8th. of material present. The builder needs to repair all the locations where the Cement Stucco is not applied correctly before the warranty expires. *When you are told by the builder that a representative of their company will be coming to your House to address my findings, please call me ahead of this scheduled time so I can be present to show the Builder the many concerns I found during my inspection of the Cement Stucco (free of charge)*.
|
| 3.1 | STUCCO WEEP SCREED FLASHING Comments: Inspected |
| The metal weep flashing at the bottom of the exterior stucco walls is installed correctly. |
| 3.2 | BRICK, ROCK, VENEER Comments: Inspected |
| The imitation rock veneer is in normal condition. |
| 3.3 | SOFFITS, FASCIA, EAVES, TRIM Comments: Repair or Replace | |||
| The soffits and fascia on the house are in normal condition.
The wood trim at the bottom of all the exterior doors is not sealed with paint to prevent rot, and there are large gaps for moisture to enter the interior of the wall from rain, or if you ever washed the concrete with a hose below the doors. I find this condition on just about every new home, and always recommend the builder seal these with paint, and fill the gaps to help prevent insects from entering the walls. See the attached pictures regarding this concern.
|
| 3.4 | EXTERIOR WINDOWS AND FLASHINGS, INTERIOR CONDITIONS NOTED Comments: Inspected |
| Windows in the house are dual pane glass. The conditions were
acceptable with regard to their operation and latching.
The flashing for windows installed with stucco to the edge of the window frames is not visible but there was no evidence of moisture intrusion around them inside the house. |
| 3.5 | WINDOW FRAMES Comments: Inspected |
| There was no concern with any window frame on the house.
In the future, you should periodically look at all the window frames at the exterior of the house to make sure gaps between the stucco and the metal frames have not occurred, which is a possibility in the future from expansion, contraction, and normal shrinkage of building materials. If cracks, or gaps appear, they should be caulked with a paintable caulk. |
| 3.6 | EXTERIOR DOORS AND WEATHER STRIPPING Comments: Inspected |
| The exterior entrance doors operated and latched correctly when inspected. The weather stripping around the frames was functional. |
| 3.7 | DOOR BELL Comments: Inspected |
| The door bell operated. |
| 3.8 | DECKS, BALCONIES, RAISED DECKS, STEPS, RAILINGS Comments: Inspected | |
The rear deck was in normal condition, the floor covering is skid &
water resistant as required. The guardrails are secured to the outer
perimeter of the deck correctly.
|
| 3.9 | EXTERIOR SHEETROCK CEILINGS, EXTERIOR CEILING FANS Comments: Inspected |
| The sheetrock on the exterior patio ceilings is in normal condition
today.
In the future you may notice shrinkage cracks occur where the sheetrock meets the walls, the minor cracks are basically unavoidable because of the drastic temperature variations in Arizona, expansion and contraction occurs. You could caulk any cracks in the future with a high grade paintable caulk which will expand and contract with the material it is applied to if necessary. |
| 3.10 | EXTERIOR ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Exterior electrical receptacles are Ground Fault Circuit Interrupters.
All exterior receptacles were tested, they tripped when I manually
tested them.
The Lighting operated when inspected, some fixtures which have burnt bulbs did have power to them. |
| 3.11 | EXTERIOR PLUMBING, FAUCETS Comments: Inspected |
| Hose faucets are present at front and rear of the home. They operated properly at the time of this inspection. |
| 3.12 | FIREPLACE CHIMNEY(S) EXTERIOR/INTERIOR AND FLASHING Comments: Inspected |
| The exterior of the two chimneys were inspected for conditions
which could jeopardize the safety of the home occupants.
Construction was consistent with current building standards.
The flue pipes for both natural gas fireplaces are double wall Metal Type B , there was no visible concern present today. The metal flashing around the Chimneys was installed correctly on the roof. Here is a link for more information about Fireplace Chimneys. |
Inspection Items
|
| 4.0 | ROOF COVERINGS, TYPE, CONDITION Comments: Inspected | ||||
| The roof system was inspected by walking it. The roof covering is Cement Tile, with an asphalt-fiberglass membrane under the tiles, which is what actually keeps the water out of your house.
There was no concern with the roof covering at the time of this inspection. Here is a link that will give you additional information about your roof system.
|
| 4.1 | ROOF FLASHINGS, DRIP EDGE FLASHING Comments: Repair or Replace | |||||
| At the west side front of the house at the second portion of the roof at the circular area there is a
Kickout Flashing installed wrong.
The builder needs to make the repair as soon as possible before you experience interior moisture damage to your house.
|
| 4.2 | PATIO ROOF COVERINGS, FLASHINGS, DRIP EDGE FLASHING Comments: Inspected |
| The rear patio roof which is actually the deck over the rear patio was in normal condition today. The metal drip edge flashings were installed correctly. |
| 4.3 | ROOF PENETRATIONS, PLUMBING VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, CONDITION Comments: Inspected |
| The metal flashing around the roof penetrations such as plumbing vents, chimneys, and attic vents are installed correctly. There was no sign of any moisture penetration around them in the attic which would tell you they are not sealed or installed correctly also. |
| 4.4 | ROOF SHEATHING Comments: Inspected |
| The roof sheathing was inspected in the attic where access could be obtained. There was no concern present. |
| 4.5 | ROOF DRAINAGE SYSTEMS Comments: Not Tested |
| There is no roof drainage system on this home. Roof gutters will help preserve the building components below the roof line if you have them installed. |
INSULATION: Blown Cellulose |
Inspection Items
|
| 5.0 | ATTIC ACCESS Comments: Inspected |
| Attic access was gained through a scuttle opening in the ceiling with a ladder at master bedroom closet. |
| 5.1 | INSULATION AND VAPOR RETARDERS, TYPE VISIBLE Comments: Inspected | ||
Attic insulation was visually inspected while I was in the attic, the Blown Cellulose Insulation is
properly distributed and R-Value (resistance) is consistent with current standards.
|
| 5.2 | ATTIC VENTILATION Comments: Inspected |
| There is passive ventilation for the Attic. Stationary Roof Vents, and
Gable Vents, which allow air to flow through your attic which helps
keep the Attic cooler in the summer, and helps keep your cooling
bills down during our long hot Arizona summers.
In the winter, the ventilation really does not cause any concerns when the conditioning system is in the Heating mode, the sun heats the attic to just about the same temperature as the inside of the house during the day. |
| 5.3 | ROOF UNDERLAYMENT, FRAMING, VISIBLE Comments: Inspected |
| Roof framing was inspected while in the attic, I found no cut, altered, or damaged components visible. |
| 5.4 | EXPOSED ATTIC WIRING CONDITION Comments: Inspected |
| The electrical wiring which is visible and not covered with insulation was correctly installed. Wires are generally located throughout the attic area of a building under the insulation. When modifications have been made they are sometimes visible. We report when the wiring methods are not consistent with the current electrical codes. |
| 5.5 | BATHROOM CEILING VENTILATION DUCTS, DRYER VENT PIPES, FLUE PIPES Comments: Inspected |
| The flexible and ridged Metal duct piping for Interior Ventilation Fans, Water Heater, Furnace Flues, Dryer Vent Pipe were installed correctly in the attic and terminated above the roof as required. |
Inspection Items
|
| 6.0 | MAIN WATER SHUTOFF DEVICE, LOCATION Comments: Inspected | |
The water shutoff valve to turn off all the water to the home is located
at the right side front of the house, the exterior plumbing pipe is
copper going into the ground toward the City Water Meter located
behind the sidewalk.
|
| 6.1 | ELECTRICAL BONDING WIRE AND CLAMP Comments: Inspected | |
| The electrical system is Bonded to the water pipe at the main
supply line coming into the building correctly.
The clamp the Copper Wire is attached to is fastened to the Copper Water Line correctly.
|
| 6.2 | INTERIOR WATER SUPPLY MATERIAL, DISTRIBUTION SYSTEM, AND SUPPORTS Comments: Inspected |
| The interior water supply piping is Copper where the pipes are
visible. There was no concern with the pipes or supports in the
home where I could actually see them.
This house could also have PEX Plastic piping inside walls and through the attic buried in the insulation, but I did not see any tag in the electrical distribution panel stating this for a fact, or did I find a Manifold for PEX Piping. Many new homes could have both Copper and PEX Plastic Piping, which is widely used in new construction, sometimes the PEX is not visible. |
| 6.3 | INTERIOR DRAIN, WASTE AND VENT PIPE MATERIAL, AND SUPPORTS Comments: Inspected |
| Interior drains and the drainage vent pipes are constructed of ABS
and PVC plastic piping.
There was no concern with any visible pipes or supports. |
| 6.4 | WATER HEATER(S) AND SYSTEM Comments: Repair or Replace | ||||
| Hot water heater is natural gas manufactured by A.O.Smith in
2006 with a capacity of 50 gallons located in the garage.
Plumbing, and Venting connections are consistent with current
building standards.
The Appliance Connector CSST is not long enough, the tubing is very tight against the water heater with pressure on the fitting. I recommend the builder replace the Appliance Connector with a longer one to possibly prevent a natural gas leak or fitting failure at the connection (see picture) What the water heater is sitting on in the garage is wood framed with sheetrock covering the framing material. The sheetrock is damaged and needs to be repaired. The water softener discharge pipe is leaking at the fitting near the wall in back of the unit (as pictured). The fitting needs to be tightened to stop the leak.
|
| 6.5 | GAS METER AND SHUTOFF Comments: Inspected | |
The natural gas meter and shutoff valve is located at the right side
front of the House in case of an emergency, to shut off all gas going
into the house.
|
| 6.6 | SEWER CLEANOUTS Comments: Inspected |
| The sanitary sewer cleanouts are accessible at the front of the home going to the public sewage system. |
Inspection Items
|
| 7.0 | MAIN ELECTRICAL METER AND DISTRIBUTION PANEL LOCATION Comments: Inspected |
| Main electrical service Meter and Distribution Panels are located at the right side front of the home. |
| 7.1 | MAIN ELECTRICAL PANEL AND DISTRIBUTION PANEL CONDITION Comments: Inspected |
| The electrical equipment was installed in a professional like manner. |
| 7.2 | MAIN ELECTRICAL SERVICE CONDUCTORS, TYPE, AMPERAGE AND VOLTAGE Comments: Inspected |
| The main Electrical Service Conductors providing power from the
municipal supplier are Underground.
The type of Conductors (wires) from the Meter Panel to the Distribution Panel are Copper 120/240 Volt, 200 Amp. single phase. |
| 7.3 | MAIN OVERLOAD DEVICE AND THE ELECTRICAL SYSTEM GROUNDING Comments: Inspected | |
| The main overload device to turn All electrical power off to the entire
home is a 200 Amp. Single Throw Circuit Breaker (see picture).
A copper grounding conductor for this electrical system is visible in main service distribution panel, correctly installed and presumed to terminate to the foundation. The exact termination point is not visible because the conductor is installed inside the wall cavity. Grounding was tested at receptacles in the building.
|
| 7.4 | BRANCH CIRCUIT WIRE TYPE AND CIRCUIT BREAKERS Comments: Inspected | |
| Branch circuit wires in the Distribution Panel are Copper 120/240
Volt and Aluminum 240 Volt feeding electricity to the various circuits
throughout the house. The Overload Devices the wires are
connected to are Circuit Breakers.
Branch circuit wires are professionally installed in distribution panel, there are no concerns present with regard to the wire compatibility (size) to the circuit breakers they are attached to.
|
FORCED AIR FURNACE(S): Two Gas Forced Air Furnaces | CONDENSER-COMPRESSOR: Two |
Inspection Items
|
| 8.0 | AIR CONDITIONING EQUIPMENT AND AIR HANDLER(S) Comments: Inspected | |||
| The Air Conditioning system for the home is Two Goodman 2006
Condensing Units located at the exterior of the House on the (west
side). The Two Goodman Air Handlers (blowers, evaporator coils)
are located in the attic.
These Goodman Air Handlers have Gas Forced Air Furnaces located inside the equipment in the attic, please see the Heating section of this report. I explain that the Furnaces are located in the Air Handlers in this Cooling section of the report to avoid confusion for someone who may not know this.
|
| 8.1 | CONDENSATE DRAIN LINES, SYSTEM OVERFLOW PAN AT THE EQUIPMENT Comments: Repair or Replace | |
| The condensation Drip Pans attached to the bottom of both Air
Handlers (evaporator coils) is blown Cellulose Insulation, which will
plug the secondary drain if condensation water ever dripped into the
pan.
The builder needs to have both Drip Pans cleaned of insulation. If condensation water did enter the drip pan and the drain became plugged the water would overflow into the house ceiling, which could cause major repairs necessary in the future.
|
| 8.2 | REFRIGERANT LINES FOR AC EQUIPMENT Comments: Repair or Replace | |
| There is insulation missing from the Refrigerant Line feeding the Air
Conditioning Unit on the left side when you enter the attic from the
master bedroom closet.
The Foam type insulation helps the refrigerant line from sweating in the summer when the attic is hot, and the refrigerant line is cold. If the refrigerant line began to sweat the water could drip on the second floor ceiling below, causing moisture stains and damage to the sheetrock.
|
| 8.3 | HEATING EQUIPMENT AND AIR HANDLER(S) Comments: Inspected | ||
| The home has two Goodman Gas Forced Air Furnaces in the Air
Handlers located in the attic. Operating the equipment at the time of
this inspection there was no concern with the system. The
equipment was inspected for the correct installation methods.
The supply temperature from various register vents was on the average 114-116 degrees (normal).
|
| 8.4 | HEATING EQUIPMENT FLUE VENT PIPES Comments: Inspected |
| The flue vent pipes for the gas furnace(s) were inspected for correct installation (fastening) and proper termination above the roof. The flue pipes vent carbon monoxide to the exterior, the by-product of a combustible gas. |
| 8.5 | ELECTRICAL DISCONNECTS, WIRING, CONDUIT, FOR THE HEATING AND COOLING Comments: Inspected | |
| The electrical disconnects for the conditioning system(s) are
installed correctly at the exterior wall of the home in back of the
units. The electrical power can also be turned off at the electrical
distribution panel. The disconnect at the units outside is for
emergencies and service technicians.
There is also a switch next to each Air Handler in the attic to turn off the power to the equipment, generally used by service technicians.
|
| 8.6 | DISTRIBUTION DUCTS, REGISTERS, PIPING, SUPPORTS, FILTERS Comments: Inspected | |
| Heat and Cooling distribution ducts and register vents were
inspected. Distribution ducts are insulated flexible type and
insulated metal type located in the attic and also in the ceilings of
the house.
The return Air Filters are located in the second floor hallway ceiling (three) 20x25x1 size disposable type filters which should be changed at least every other month or sooner if needed.
|
| 8.7 | THERMOSTAT(S) Comments: Inspected |
| Thermostats are located in main hallway at the first and second floor of the house, properly fastened to the wall and operated as intended in both the Heating and Cooling modes. |
| 8.8 | REGISTER VENTS Comments: Inspected |
| There was no concern present with any heating and cooling registers in the house, they all had normal air flow at the time of this inspection. |
Inspection Items
|
| 9.0 | FLOORS Comments: Repair or Replace | ||
| The floor in the master bathroom squeaks when I walked across it,
which tells me the subfloor is not attached to the framing correctly.
This is not a structural defect but is annoying to some people.
I would have the builder make the necessary repairs needed to attach the subfloor to the framing components correctly to stop the noise. Next to the master bath tub there is tile grout missing, repair is also needed at that location.
|
| 9.1 | WALLS, CEILINGS Comments: Repair or Replace | |
| Walls and ceilings have minor settlement and shrinkage cracks
which are located at various areas throughout the home. This is
common for new homes. We recommend the builder repair all the
cracks and anomalies and re-paint these areas in a fashion which
would not be noticeable.
You should label all locations needing repair with Blue Painters Tape at your one year walk through with the builder.
|
| 9.2 | WALL CABINETS Comments: Inspected |
| The wall cabinets in living areas were in normal condition and fastened to the walls correctly. |
| 9.3 | INTERIOR TRIM, BASEBOARD Comments: Inspected |
| The baseboard trim at the base of the interior walls was functional (normal condition). |
| 9.4 | INTERIOR DOORS Comments: Inspected |
| Interior doors were inspected. They operated and latched properly at the time of this inspection. |
| 9.5 | CLOSET DOORS Comments: Inspected |
| The closet doors functioned as intended. |
| 9.6 | MASTER BEDROOM CLOSET Comments: Inspected |
| The condition was acceptable where visible, the home is occupied with personal belongings. |
| 9.7 | INTERIOR AND EXTERIOR STEPS AND STAIRWAYS Comments: Inspected |
| Interior stairway was constructed to current building standards, no concerns were present. |
| 9.8 | CEILING FANS Comments: Inspected |
| Ceiling fans functioned properly when tested. |
| 9.9 | ELECTRICAL WIRING, OUTLETS, SWITCHES, AND LIGHTING Comments: Inspected |
| I tested a representative number of accessible electrical receptacles
for the correct polarity and ground throughout the House.
There was no concern with any electrical switches either. |
| 9.10 | BEDROOM ARC FAULT CIRCUIT INTERRUPTER RECEPTACLES Comments: Inspected |
| There are AFCI's, Arc Fault Circuit Interrupters connected to the bedroom wall receptacles. They tripped when I manually tested them in the electrical distribution panel outside. |
| 9.11 | FIREPLACE, INTERIOR, VISIBLE COMPONENTS Comments: Unsafe, Requires Immediate Attention | ||
| The Natural Gas Appliance Connectors are close to the Black Iron
Metal Gas Lines so the Gas Valves cannot be turned off.
Right now I cannot turn the Gas Off to the Fireplace. This is dangerous and needs to be repaired as soon as possible by the builder.
|
| 9.12 | SMOKE DETECTORS Comments: Inspected, Repair or Replace |
| Smoke Detectors were tested. They audible alarm operated
manually. I recommend that you change the batteries in the smoke
detectors every six months.
I also recommend you have Carbon Monoxide Detectors installed throughout the house and attic according to the manufacturers specifications because you have Natural Gas Appliances in the house. |
Inspection Items
|
| 10.0 | TUB SHOWER UNIT(S) Comments: Inspected |
| There were no concerns present at the time of inspection. The fixtures operated correctly. |
| 10.1 | WALK-IN SHOWER(S) Comments: Inspected | |
The condition was acceptable and the fixture operated correctly.
|
| 10.2 | MASTER BATH TUB Comments: Inspected | |
This fixture was in normal condition and functioned properly at the
time of this inspection.
|
| 10.3 | BATHROOM SINKS, COUNTERTOPS, CABINETS Comments: Inspected | |
The sinks and cabinets are functional in bathrooms.
|
| 10.4 | TOWEL HOLDERS Comments: Inspected |
| There was no concern present. |
| 10.5 | DRAINAGE PIPES Comments: Inspected |
| There were no active leaks at the time of this inspection. |
| 10.6 | WATER VALVES Comments: Inspected |
| There were no active leaks at the time of this inspection. |
| 10.7 | TOILETS Comments: Repair or Replace |
| The toilet in the first floor bathroom might need a new wax seal
installed under the toilet, I can smell sewer gas.
Many times the plumber does not line the wax seal up correctly with the drain below the toilet or forgets to install one. Unbolting the toilet from the floor and looking is the only way to see for sure if the wax seal is installed correctly. I would mention this concern to the builder before your warranty expires. |
| 10.8 | BATHROOM , WATER PRESSURE, AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected |
| The water pressure in the bathrooms was normal. The drains emptied correctly. |
| 10.9 | BATHROOM, ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Ground fault circuit interrupters were tested in bathroom(s), no concerns were present. The lighting functioned properly. |
| 10.10 | BATHROOM EXHAUST VENTILATION Comments: Inspected |
| Bathroom ceiling ventilation fans were functional. |
Inspection Items
|
| 11.0 | KITCHEN CABINETS AND COUNTERTOPS Comments: Inspected | |
Cabinets and countertops are in normal condition, the cabinets are
fastened to the walls correctly, and the granite countertops are also
correctly installed.
|
| 11.1 | KITCHEN SINK AND FAUCET Comments: Inspected |
| The faucet operated correctly. The sink was in normal condition. |
| 11.2 | SINK DRAINAGE PIPES Comments: Inspected |
| There were no active leaks at the time of this inspection. |
| 11.3 | SINK WATER SUPPLY PIPING Comments: Inspected |
| There were no leaks at the time of this inspection. |
| 11.4 | WATER PRESSURE AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected |
| The water pressure was acceptable and drains emptied correctly. |
| 11.5 | KITCHEN ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Ground Fault Circuit Interrupters were tested. Lighting functioned correctly. |
| 11.6 | FOOD DISPOSER Comments: Inspected | |
Disposer functioned properly. Electrical and plumbing connections
were consistent with current standards.
|
| 11.7 | DISHWASHER Comments: Inspected |
| I operated the dishwasher manually through a rinse cycle (functioned properly). Plumbing and electrical connections are consistent with current standards. |
| 11.8 | RANGE AND OVEN Comments: Repair or Replace | |
| The Electric Oven has not functioned since the buyer closed
escrow, he said that after numerous calls to the builder he was
referred to other subcontractors who performed work on the House
which is not the responsibility of the Home Owner, it is the
responsibility of the Builder to either repair it, or replace it.
I would file a formal complaint with the Arizona Registrar of Contractors against the Builder and explain you have not had an Oven that has functioned in 11 months after you closed escrow.
|
| 11.9 | RANGE VENTILATION Comments: Inspected |
| Range vent hood is forced exterior exhaust type and operated as intended. |
| 11.10 | MICROWAVE Comments: Inspected |
| Microwave was tested to heat a wet paper towel and operated correctly today. |
| 11.11 | REFRIGERATOR Comments: Inspected |
| The refrigerator-freezer was operating today. |
Inspection Items
|
| 12.0 | PLUMBING CONNECTIONS FOR WASHER Comments: Inspected |
| Plumbing connections for a washing machine are consistent with current plumbing standards. |
| 12.1 | DRYER AND POWER SUPPLY Comments: Inspected |
| The power supply to operate a dryer is 240 Volt electricity. |
| 12.2 | DRYER VENTING Comments: Repair or Replace | |
The Dryer is not connected to the vent pipe so the air will blow to
the exterior of the House. I suggest going to a Home Improvement
Store and buy a Dryer Vent Connection Kit.
|
| 12.3 | ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Receptacles and switches were tested, no concerns were present. |
| 12.4 | ROOM EXHAUST VENTILATION Comments: Inspected |
| Laundry room has an exterior vented ceiling fan which operated properly when inspected. |
| 12.5 | SINK OR WASH BASIN Comments: Inspected | |
The sink operated correctly, there were no leaks present at any
plumbing connections.
|
Inspection Items
|
| 13.0 | PASSAGE DOOR TO INTERIOR/EXTERIOR Comments: Inspected |
| Passage door to the interior of the house is self-closing and fire rated (which is required). Operation was acceptable. |
| 13.1 | FLOORS, WALLS, CEILINGS Comments: Repair or Replace | |
| The concrete floor is sloped backwards, when it rains water seeps
under the garage doors and puddles on the floor.
When I was at the house today it has not rained for days and rain water was still lying on the garage floor. The builder needs to correct this so water flows toward the street, which is required with all new construction.
|
| 13.2 | GARAGE DOOR MATERIAL AND CONDITION Comments: Inspected |
| Garage doors are metal, the condition was normal. |
| 13.3 | GARAGE DOOR OPERATING TRACKS Comments: Inspected |
| There was no concern present. |
| 13.4 | GARAGE DOOR OPENER(s) Comments: Inspected |
| The Automatic Door Openers functioned properly when met with reasonable resistance (reversed), photo-electric eyes are present and operational so the door will reverse if someone walks under the door while it is closing (required on all garage doors since 1993). |
| 13.5 | ELECTRICAL RECEPTACLES, LIGHTING Comments: Inspected |
| Ground Fault Circuit Interrupters functioned correctly, lighting and switches also operated correctly. |
| 13.6 | GARAGE DOOR TRIM Comments: Inspected |
| There was no concern with the garage door trim at the exterior perimeter of each door. |
![]() Inspect Arizona Companies, Inc.
10599 E. Betony Dr. |
|
Customer |
|
Property Address |
|
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the building.
This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
| 1. GENERAL BUILDING AND SITE INFORMATION | ||||||||||||
|
| 3. EXTERIOR OF BUILDING, MATERIALS USED AND CONDITION | ||||||||||||
|
| 4. ROOF MATERIAL TYPE AND CONDITION | ||||||
|
| 6. PLUMBING SYSTEMS OF THE BUILDING | ||||||
|
| 8. AIR CONDITIONING AND HEATING EQUIPMENT | ||||||||||||
|
| 9. INTERIOR OF THE ENTIRE BUILDING | ||||||||||||||||||||||||
|
| 10. BATHROOM(S) | ||||||
|
| 11. KITCHEN, CABINETS, COUNTERTOPS, APPLIANCES | ||||||
|
| 12. LAUNDRY ROOM | ||||||
|
| 13. GARAGE, DOORS, AUTO-OPENERS | ||||||
|
The Masonry Fence has not been repaired after the drain was installed. Masonry Block companies make "Perforated Blocks" which should be installed at this location in my opinion, rather than the "Black Plastic Drain Cover" (as pictured).
All soil grades when the lot is rough graded are required to slope away from the house foundation and toward the street before any landscape rock or grass is installed. The reason for this is water accumulating next to your house foundation, or masonry fence can cause soil to expand if the soil has expansive characteristics.
Please read this document regarding Arizona Expansive Soils , this link provides you with additional information about Arizona soils, and why it is important to have the Builder correct the soil grade and (slope) of your lot if expansive soils are present.