| Date: 2/22/2011 | Time: 09:00 AM | Report ID: 2.22.11 |
| Property: 876 Palm Tree Dr. Scottsdale AZ 85254 |
Customer: Sample Report |
Real
Estate Professional: Mike Jones Re/Max |
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor or professional.
Inspected: This term means I visually observed the system, component, or unit, and if no other comments were made then it appeared to be functioning as intended allowing normal wear and tear. The notation does not mean that the item is perfect, but does meet a reasonable standard on the day of inspection.
Repair or Replace: The item, component, or system is not functioning as intended or needs further inspection by a qualified contractor. Items, components, or units that can be repaired to satisfactory condition may not need replacement.
Requires Immediate Attention: The item, component, system, or unit needs immediate attention by a qualified professional or contractor for the safety or health of the occupants of the building. Could cause further major deterioration, or complete failure of a system or component. Worsen appreciably, cause damage, or be a serious safety hazard.
Unsafe: A condition in a readily accessible installed system or component which is judged to be a significant risk of personal injury during normal day to day use. The risk may be due to damage, deterioration, improper installation, or a change in adopted construction standards.
Not Tested: I did inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not testing or operating.
Informational: Specific information regarding a system, component, or item, will be described in the report.
IMPORTANT NOTICE TO THIRD PARTIES: Receipt of this report by anyone other than the above listed party(s) is not authorized by Inspect Arizona Companies, Inc. This report is prepared for the sole and exclusive use for the client who signed the INSPECTION AGREEMENT and is subject to the terms and conditions agreed upon. This Inspection Report is a product, and is copyrighted by Inspect Arizona Companies, Inc. at the date of this inspection. Duplication by any means whatsoever is prohibited without prior written permission and authorization from Inspect Arizona Companies, Inc. Unauthorized duplication, use, or reliance of this report shall constitute all parties agreed upon to hold harmless, whether individual, joint or otherwise, Dale Duffy and Inspect Arizona Companies, Inc., their successor's and assignee's.
PERMITS/BUILDING CODE VIOLATIONS: If you are concerned about code violations or building permit information you should contact the City Building Department the building is located in for further information.
You have contracted with us to perform an inspection
in accordance with Arizona industry standards for the inspection profession.
This is different from our technically exhaustive inspection which takes all day
to complete, involves the use of specialized instruments, the dismantling of
equipment, video scanning, destructive testing and laboratory analysis of
possible contaminates. Our purpose is to identify defects or adverse conditions
that need additional evaluation, are safety concerns, or may lead to costs that
would significantly affect your evaluation of the property at the time of this
inspection:
The
Arizona minimum Standards for Professional Practice are available online.
Please read this!
|
Client Is
Present: Yes |
Age of
House: 1997 |
House Faces: South |
|
Weather
Conditions: Clear |
Approximate
Temperature: Over 65 degrees |
Rain in last 3
days: Yes |
![]() |
![]() |
|
Items |
| 1.0 | INSPECTION REPORT INFORMATION Comments: Informational |
| Hello Mr. Sample,
Thank you for allowing us to inspect your future home. During the time you own the house you may call me anytime for any reason. At the end of this report we have compiled a list of trustworthy Licensed Contractors. They are all licensed professionals and will not take advantage of you, many of my past clients have used their services including myself, I have never heard a complaint from anyone. If you have any questions-concerns after you receive this Inspection Report or after you move in do not hesitate to call me, any further help regarding the home is always free. I am available day or night, you may call anytime, including weekends. Informational: Throughout this Inspection Report I have inserted various "Links" you may click on which will take you to other websites or other informational pages on the internet to help you understand various terms written in this Inspection Report. The (Example) "Links" are safe to click, they are trusted service providers or other information geared at helping you understand various terms in the report you may not be familar with. Thank You, Dale M. Duffy Inspect Arizona Companies,
Inc. |
| 1.1 | GENERAL
EXTERIOR SITE DRAINAGE Comments: Repair or Replace | ||||||
| Drainage away from
the foundation of the home needs to be improved so water will flow away
from the foundation and toward the street around the entire house. Any
location water cannot flow away from the foundation moist soil has the
possibility to attract (click
link) wood destroying
insects . Concrete foundation
deterioration occurs, and possible foundation damage from (click link) expansive
soil . Please see the attached photos for
additional information and locations.
There should be at 6-8 inches of free clearance from the base of the exterior walls to final grade with the soil sloped 1/4 inch per foot away from the foundation. I highly recommend you have a qualified landscaper grade the soil around the home properly so water flows away from the foundation and toward the street.
|
| 1.2 | TREE OR
VEGETATION NEXT TO THE BUILDING Comments: Repair or Replace | ||
| I recommend
trimming any tree branches in direct contact with the home. The wind
moving branches will cause damage to building components (roof, fascia,
stucco).
Trees at the west side of the house in the City Common Areas are planted to close to the Masonry Fence, the roots are lifting the Masonry Fence causing damage. Trees-Vegetation are also damaging the Fence at the north side of the property, also associated with vegetation planted to close to a Masonry Product, roots lifting the Fence causing damage.
|
| 1.3 | DRIVEWAY,
PARKING LOT, WALKWAYS, PATIOS, ENTRYWAYS, CONDITION Comments: Inspected |
| The exterior hard surfaces were in normal condition at the time of this inspection. Minor cracks in concrete are normal, considered typical, and cracks in hard surfaces are found at all properties. |
| 1.4 | FENCE AND
GATE(S), CONDITION Comments: Repair or Replace, Unsafe | ||
| Both Gates need
Self Closing Devices functional so they Self Close and Latch (Pool
Safety). A law in Maricopa County which could save a Childs life.
The Masonry Block Fence around the property is serving its purpose, but there is damage (cracks) because Trees-Vegetation is planted to close, the roots are lifting the Fence causing damage. You should contact the City of Scottsdale regarding what is occurring to the Masonry Fence. The Trees in the common area by the sidewalk at the west side of the property should be removed or the roots will continually cause damage to the Fence until it possibly collapses.
|
| 1.5 | IRRIGATION SYSTEMS Comments: Repair or Replace | |||
| Sprinkler &
Drip Irrigation Systems are not part of a Home Inspection according to
Arizona Law but I do note obvious deficiencies as a courtesy to my
clients. I operated each accessible Zone manually by turning on the valves
in the Irrigation Control Box(s) at the front of the house. I could not
find the Irrigation Control Box for the backyard, therefore the backyard
watering system was not tested.
The Timer is located at the southeast exterior wall of the garage, programmed to operate automatically. I tested the front zones manually by turning on the solenoids in the irrigation control box. There are various Drip Heads and 1/4 inch supply lines broken-cracked-split spraying water. Have a Landscaper or Handyman go over the entire system and repair as needed.
|
|
Items |
| 2.0 | FOUNDATION TYPE; CONDITION Comments: Inspected |
| The foundation of this house is a (Click Link) Monolithically Poured Concrete Slab. No concerns were visible at the time of inspection. Minor cracks are common in all concrete products and the condition of this foundation is considered typical or normal at all locations I could see the Concrete Slab. |
| 2.1 | FLOOR
TYPE; CONDITION Comments: Inspected |
| The floors in the house are a Monolithic Concrete Slab at the first floor and Wood Framing at the second floor. There are floor coverings installed over the floors, but there was no visual evidence of a concern such as major wall or ceiling cracks which would lead me to other conclusions of the existing condition. |
| 2.2 | EXTERIOR
AND INTERIOR LOAD BEARING WALLS; TYPE; CONDITION Comments: Inspected |
| The exterior and interior walls are constructed with Wood Framing Materials (2x6 construction). The walls are covered with sheetrock at the interior. There was no visible concern with the wall framing structurally. |
| 2.3 | CEILING
MATERIAL; TYPE; CONDITION Comments: Inspected |
| The ceilings in the building are constructed with Wood Framing Materials and Sheetrock. There was no evidence any concern is present structurally. |
| 2.4 | ROOF
STRUCTURE TYPE; CONDITION Comments: Inspected |
| The roof system is built with Engineered Wood Trusses-Rafters and Oriented Strand Board (OSB) roof sheathing (decking). Inspecting the condition of the components in the attic there was no concern present today. |
| 2.5 | POSTS,
BEAMS, COLUMNS TYPE; CONDITION Comments: Inspected |
| There was no concern present with any visible wood or concrete Post, Beam, or Column, which are load bearing components of the building (structurally). |
![]() |
![]() |
|
Items |
| 3.0 | ROOF
COVERINGS, TYPE, CONDITION Comments: Repair or Replace | ||||||||||||||||||||
| The roof system
was inspected by walking the surface. There are many repairs need at
the Concrete Tile Roof Covering. There are many Tiles sliding from their
intended position, cracked Tiles, loose Tiles (see photos). At the
southwest corner of the house there is Modified Bitumen installed in a
valley, the material needs to be replaced (small area of Modified-Roll
Roofing material). The Roll Material is cracked-split and debris on the
roof is not allowing water to flow off this portion of the roof system.
Water is entering the Garage, there are various moisture stains with
moisture present today (tested with Moisture Meter and Thermal Imaging
Camera).
The 2x4 Wood installed to support the Ridge-Cap Tiles is exposed at numerous locations over the entire roof (bare wood). The Cap Tiles should be removed so new Felt Underlayment can be wrapped over-around the 2x4 so it does not become deteriorated in the future. Any location I could see the bare wood it looked to be in normal condition now. The Felt is deteriorated-torn-cracked-missing which should be replaced at the 2x4's and any other locations water is entering the house. The Tiles will need to be removed by a Roofing Contractor to perform this repair. I suggest having at least three Licensed Roofing Contractors give you repair estimates after reviewing the entire roof covering, or you can forward this report to a roof contractor if they would like to see what the concerns are before even going to the property. The cost will be significant, meaning over $1,000.00 in my professional opinion. I do not receive any compensation whatsoever from any Contractor I refer, they are simply the only Contractors who have either done work for me personally, or I have inspected work other people have hired them to do. Tile Roof Information: Tiles do not protect a building from water intrusion, they simply protect the Water Resistant Membrane under the Tiles (known as underlayment) from the sun, wind, and physical damage.
|
| 3.1 | ROOF
UNDERLAYMENT, MEMBRANE, FELT, WATERPROOFING MATERIAL Comments: Repair or Replace, Informational | ||
| The Felt Type
Membrane Underlayment under the Concrete Tiles is what keeps rain water
out of any building with a Concrete Tile Roof Covering. Tiles protect the
Membrane from the sun which deteriorates the Membrane very fast if exposed
to the sun. Tiles are also installed to make a building look presentable
naturally, but the primary reason tiles are installed on a roof is to
protect the waterproofing membrane from the sun, wind, and physical
damage.
In all actuality all the Concrete Tiles could be removed and the roof should not leak if the membrane is in normal condition. The membrane under the Tiles usually lasts about 18-25 years before the Tiles will need to be removed and a new membrane installed, the difference in time spans depends on the quality of the membrane. The Membrane-Underlayment on this roof looks like 90 lb. Felt, which was a typical installation method-material installed when this house was built in the late 90's. Now many builders install a higher quality Felt type Membrane with woven fiberglass in the material which lasts much longer than 90 lb. Felt. The only way to determine the exact condition of the underlayment is have a Licensed Roofing Contractor look under Tiles in the field of the roof covering, which should not deter you from having this performed before your inspection contingency period ends. As pictured, the Felt is deteriorated at the Ridges, under Cap Tiles.
|
| 3.2 | FLASHINGS, DRIP EDGE FLASHING Comments: Inspected, Repair or Replace, Informational |
| The Metal
Flashings at the roof valleys need the Debris-Leaves removed so water
will flow from the roof as intended. Water backing up on the roof surface
will allow leaks to occur.
Informational: Flashing is an impervious material (usually galvanized or aluminum sheet metal) that comes in a variety of shapes and sizes and is used to cover, waterproof, and direct water away from roof penetrations and from intersections between the roof covering and other materials. |
| 3.3 | ROOF
PENETRATIONS, PLUMBING VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, AC-DUCTS,
FLASHING CONDITION Comments: Repair or Replace | |||||
There is a
Plumbing Vent Pipe (north side of roof) which is not Flashed properly with
the Metal wrapped into the Pipe so rain water cannot flow between the Pipe
and the Metal Flashing (as pictured). Have the Roofing Contractor install
the Flashing appropriately.
|
| 3.4 | METAL
DIVERTER FLASHING(S) (designed to divert water away from wall-roof
corners, edges) Comments: Repair or Replace, Informational |
| All the Kick-Out Diverter Flashings need the debris-leaves dirt, etc; removed, cleaned so water can flow from the roof as intended. |
The
heating and cooling systems should be inspected and serviced on an annual
basis.
I recommend obtaining from the seller well before close of
escrow any documents concerning regular maintenance and service. If it cannot be
proven that the heating and cooling systems have been inspected and
serviced within the past twelve months, I recommend a complete system evaluation
by a qualified heating and cooling specialist before your inspection contingency
period ends.
|
FORCED AIR
FURNACE(S): Two Natural Gas Forced Air Furnaces Trane Automatic Safety Controls Were Tested |
CONDENSER-COMPRESSOR: Two Trane Automatic Safety Controls Tested |
|
Items |
| 4.0 | AIR
CONDITIONING EQUIPMENT AND AIR HANDLER(S) Comments: Inspected, Informational | ||||
| The Air Conditioning System for
the home is Two 1997 Trane Split System 240 volt Electric Condensers
located at the exterior of the home (west). The Trane Air Handlers Fans,
Indoor Coils, Trane Natural Gas Furnaces are located in the attic. The
energy source for the cooling system is 120/240 volt electricity, the
energy source for the furnace is natural gas and 120 volt electricity.
Testing the system in the cooling mode the supply temperature was 48-54 degrees, testing the system in the heating mode the supply temperature was 105-118 degrees on average which is normal for this type of heating & cooling system. All heating and cooling systems need to be serviced yearly by a qualified professional so they operate efficiently. Refrigerant pressures need to be checked and the condenser coils cleaned. A system supplying air even one or two degrees lower after service will reduce your electrical consumption.
|
| 4.1 | CONDENSATE DRAIN PIPES, OVERFLOW DRIP PAN BELOW THE AIR
CONDITIONING EQUIPMENT Comments: Inspected, Informational | ||
The condensate drainage lines at the
Evaporator Coil(s) of the Air Handler(s) are installed correctly where I
could see the PVC plastic piping. The drip/overflow pan(s) is installed
correctly also.
|
| 4.2 | ELECTRICAL DISCONNECTS, WIRING, CONDUIT Comments: Inspected |
| The electrical disconnect(s) and wiring (in weather protective conduit) for the Air Conditioning System was installed correctly mounted on the exterior wall of the house in back of the units. The Electrical Disconnect(s) are installed for an air conditioning service technician for his safety while working on the equipment. |
| 4.3 | REFRIGERANT LINES FOR AC EQUIPMENT Comments: Repair or Replace | ||
The refrigerant
line at the First Air Handler in the attic needs the Foam Insulation
repaired, there is a piece missing allowing the refrigerate pipe to sweat
during hot summer months, I could see where the condensation from the
refrigerate pipe has been dripping on top of the Air Handler-Gas Furnace
(as pictured). When you have the Conditioning Equipment Serviced have the
HVAC Technician place a small piece of Foam Insulation on the Refrigerate
Pipe to stop condensation from forming-dripping.
|
| 4.4 | HEATING
EQUIPMENT FLUE VENT PIPES Comments: Inspected, Informational |
| The Metal Flue Vent pipes for the natural gas furnace(s) were inspected for correct installation (fastening-support) and proper termination above the roof of the building. The flue(s) vent carbon monoxide to the exterior, the by-product of a combustible gas. |
| 4.5 | INTERIOR
NATURAL GAS PIPING FOR FURNACE(S), TYPE, SUPPORTS, CLAMPS,
STRAPS Comments: Inspected, Informational |
| The Natural Gas piping in the house is both (Click link) Black Iron Pipe and (Click link) CSST Tubing, supported and installed correctly at all visible locations. |
| 4.6 | AIR
CONDITIONING DISTRIBUTION DUCTS, TYPE, SUPPORTS, CONDITION,
RECOMMENDATIONS, CONSIDERATIONS Comments: Inspected | ||
Distribution ducts are (Click link) Insulated Flexible
type located throughout the attic connected to supply registers throughout
the house. They are supported correctly with nylon straps where I can
actually see them (limited view at some locations).
|
| 4.7 | AIR
CONDITIONING SUPPLY REGISTERS Comments: Inspected, Informational | ||||||||
| There was conditioned air in all
habitable rooms from the Air Conditioning Equipment (heat & cool air).
I do not judge the air flow, only a licensed HVAC contractor performing a
air flow rate check could determine if the system is distributing air
properly. I tested the Supply Temperatures from each Register using a
Thermal Imaging Camera, there was no concern with the supply temperatures.
Upgrading supply air registers to new registers which have much better adjustment available would allow you to control air flow from supply registers significantly better.
|
| 4.8 | AIR
CONDITIONING RETURN AIR FILTER(S), LOCATION, TYPE, SIZE, RECOMMENDATIONS,
CONSIDERATIONS Comments: Repair or Replace, Informational | |||
| There are Two
20x30x1 Washable Type Return Air Filters at the Hallway Ceiling of the
second floor. You should consider having the Pleated Fiberglass Disposable
Type Filters installed, they do not restrict the flow of air back to the
Air Handlers like Pleated Cloth Filters do. Allowing the conditioning
equipment to operate normally without restriction which will cause
premature failure of the conditioning system.
Every Air Conditioning Specialist I know recommends the Pleated Fiberglass Disposable type Return Air Filters.
|
| 4.9 | THERMOSTAT(S), LOCATION, TYPE, CONDITION Comments: Inspected, Informational |
| The Programmable Thermostats are properly fastened to the walls and operated as intended today, one at the first floor hallway, one at the second floor hallway. |
|
Items |
| 5.0 | MAIN
ELECTRICAL METER, SERVICE, AND DISTRIBUTION PANEL LOCATION Comments: Inspected |
| Main Electrical Service Meter Panel and Distribution Panel are located at the right side front of the garage. |
| 5.1 | MAIN
ELECTRICAL SERVICE PANEL AND DISTRIBUTION PANEL CONDITION Comments: Inspected |
| The electrical equipment was installed in a professional like manner. |
| 5.2 | MAIN
ELECTRICAL SERVICE CONDUCTORS, TYPE, AMPERAGE AND VOLTAGE Comments: Inspected |
| The Main Electrical Service Conductors providing electrical power from the municipal supplier are Underground. The type of Conductors from the Meter Panel to the Distribution Panel are Copper 120/240 Volt, 200 Amp. single phase. |
| 5.3 | MAIN
OVERLOAD-DISCONNECT DEVICE AND ELECTRICAL SYSTEM GROUND,
LOCATION Comments: Inspected, Informational | ||
| The main overload device to turn All
electrical power off to the entire home is a 200 Amp. single throw circuit
breaker at the top of the Distribution Panel (as pictured).
A copper electrode grounding conductor for this electrical system is visible in main service panel, correctly installed and presumed to terminate to the foundation. The exact termination point is not visible because the conductor is installed inside the wall cavity.
|
| 5.4 | BRANCH
CIRCUIT WIRE, TYPE, CIRCUIT BREAKERS, CONDITIONS Comments: Inspected | ||
Branch circuit wires are Copper
120/240 Volt Romex and Single Strand Conductors, and Aluminum 240 Volt
Multi Strand Conductors. The overload devices the wires are connected to
are Circuit Breakers. The conductors are properly sized (compatible) with
the Circuit Breakers they are attached to.
|
| 5.5 | ELECTRICAL REPAIRS NEEDED IN THE ELECTRICAL
PANEL(S) Comments: Repair or Replace, Informational | ||
The Conduit for
the Watering System Timer is not attached to the base of the Distribution
Panel, a Nut is needed for the threaded fitting at the end of the
watertight conduit. There is a gap at the base of the panel which could
allow mice-rodents to crawl into the panel, possibly causing a short
circuit by chewing on wires or nesting.
|
I always recommend Video Scanning all drainage systems over 15 years old before your Inspection Contingency Period Ends. If there are Trees planted in the front yard you should also have the Drain Video Scanned, roots could possibly enter the Drain Pipe causing possible problems in the future.
![]() |
|
Items |
| 6.0 | MAIN
WATER SHUTOFF VALVE, LOCATION, WATER PIPE MATERIAL TYPE, RECOMMENDATIONS,
CONSIDERATIONS Comments: Inspected, Informational | ||
| The water Shutoff Valve (Ball Valve)
to turn off all water to the house is located at the front left of the
garage, the exterior pipe is Copper plumbed into the ground toward the
City Water Meter.
I cannot see the underground-buried pipe plumbed to the City Meter, I am assuming the pipe is copper in the ground. Informational: There are also Two Ball Valves (as pictured) which turn off the water to the Yard Watering System if needed.
|
| 6.1 | ELECTRICAL BONDING WIRE AND CLAMP TO METALLIC PIPE,
CONDITION, RECOMMENDATIONS, CONSIDERATIONS Comments: Inspected, Informational |
| The electrical system is Bonded to the Metallic Water Pipe at the main supply pipe coming into the house with a Copper Conductor. The Bonding Clamp and Copper Conductor were tight. |
| 6.2 | INTERIOR
WATER SUPPLY MATERIAL TYPE, DISTRIBUTION SYSTEM CONDITION, VALVES,
SUPPORTS, RECOMMENDATIONS, CONSIDERATIONS Comments: Inspected, Informational |
| The interior water supply piping is
Copper Pipe where I could see the pipes (very limited view). There was no
visible-obvious concerns with the pipes or supports in the house. No
active leaks were observed today at water pipes, valves, or supply lines
from Valves to fixtures.
Water Supply Lines feeding water from Valves to Fixtures throughout the home are Copper, Braided Rubber, and Stainless Steel. Informational: Older Gate Valves may fail or not stop water when needed if a leak occurs at a fixture in the house. We always recommend you have older Gate Valves upgraded to new reliable Ball Valves with Woven Metal Reinforced Water Supply Lines from Valves to Fixtures. This is an upgrade all older homes should have, the cost is insignificant compared to water damage that could occur if an older Gate Valve or Supply Line failed. |
| 6.3 | INTERIOR
DRAIN WASTE AND VENT PIPE MATERIAL TYPE, SUPPORTS, RECOMMENDATIONS,
CONSIDERATIONS Comments: Inspected |
| Interior drains and the drainage vent pipes are constructed of Iron Pipe, ABS and PVC plastic piping, supported correctly where I can actually see them. |
| 6.4 | MAIN
SANITARY SEWER WASTE CLEANOUT LOCATION Comments: Inspected, Informational | |
| The Main Sanitary Sewer Cleanouts are
accessible at the front of the home (as pictured).
Informational: The Main Sewer Cleanouts are for a Plumber to professionally clean the Main Drainage-Waste Pipes if necessary.
|
| 6.5 | NATURAL
GAS METER LOCATION, MAIN GAS SHUTOFF VALVE LOCATION, PIPE TYPE, SUPPORTS,
RECOMMENDATIONS, CONSIDERATIONS Comments: Inspected | |
The Natural Gas Meter and Main Shutoff
Valve is located at the right side of the garage in case of an
emergency. The interior Gas Piping Material is (Click
link) Black
Iron and (Click link) CSST
Tubing, installed correctly where I could see it.
|
| 6.6 | WATER
HEATER(S), ENERGY SOURCE, LOCATION, RECOMMENDATIONS,
CONSIDERATIONS Comments: Inspected | ||
| You should
turn the water temperature down when you close escrow. The water
temperature was over 135 degrees today when I first began to operate
Bathroom Fixtures, any temperature over 120 degrees is especially
dangerous to Infants, small Children. Read this important Link regarding
the consequences of over-heated water.
Water Heater is natural gas (located in the garage, 2004 Whirlpool 50 gallon). Plumbing, flue venting, and gas connections were consistent with current mechanical standards. The gas supply line to the appliance is CSST Flex Tubing connected to Black Iron pipe, there was no concern with the natural gas pipes or supports. The Temperature Pressure Relief Valve (TPRV) and piping are installed correctly. The Thermocouple and the Burner is in normal condition from what I could see through the vantage point (access cover). The Type-B Double Wall Metal Flue Vent Pipes are installed correctly as well terminated above the roof one inch from comestibles. There is proper combustion air (high-low air intakes at garage wall) available for the appliance to operate as intended.
|
| 6.7 | HOT WATER
RECIRCULATING PUMP Comments: Informational |
| There is no Water Recirculating Pump installed. If you had a Licensed Plumber install the appliance at the Water Heater you would save a great amount of water waiting for heated water to Fixtures. Recirculating Pumps operate on 120 volt electricity and are economical to use compared to the cost of wasted water while waiting for heated water to arrive at Fixtures especially at the second floor. |
| 6.8 | EXTERIOR
HOSE BIBS (FAUCETS) Comments: Inspected, Informational |
| There was no concern present, the hose faucets operated correctly. Anti-Siphon Valves-Vacuum Breakers are also installed at all Hose Bibs. |
| 6.9 | WATER
SOFTENER Comments: Repair or Replace, Not Tested, Informational | ||||
| I suggest you
Google the manufacturer for operating and maintenance instructions which
are required for the system to function properly. Presently the system is
turned off with personal items piled in the Salt Tank.
I would call the company who installed the system, the label is on the front of the Filtering Tank. I do not know if the Tank has been replaced within the last year or not, but they should have a maintenance schedule of the property address if you call.
|
| 6.10 | WATER
SOFTENER DISCHARGE Comments: Inspected, Informational |
| The Water Softener discharge pipe (copper) is plumbed to the washing machine drain line, which is typical for a discharge location for the system to Back-Flush. |
![]() |
![]() |
|
INSULATION: Loose Fill Cellulose Fiberglass Batts Recommend adding more Insulation Vapor Barrier Not Required in the Phoenix area |
|
Items |
| 7.0 | ATTIC
ACCESS LOCATION(S), INFORMATION, CONDITIONS Comments: Inspected | |
Attic access was gained through a
scuttle opening with a ladder at the Master Bedroom Closet Ceiling.
|
| 7.1 | INSULATION AND VAPOR RETARDERS, TYPE VISIBLE,
VENTILATION Comments: Inspected, Informational | ||||||
| There is Loose
Fill Blown Cellulose Insulation installed properly evenly distributed, the
R-30 (resistance) is consistent with current building standards (minimum
allowable). If you had more Cellulose Insulation installed it would lower
the air conditioning costs. Cellulose Insulation is inexpensive, the costs
are recognized within a couple years in electrical savings.
Informational: I do not know what type of Insulation is installed in the walls, I cannot see it. Generally Fiberglass Batt Insulation is placed between wall framing. Using Thermal Imaging Technology I can determine if in fact there is Insulation missing, by seeing a differential in temperature at the wall. I scanned the entire wall systems, attached are a couple sample images which show no obvious anomalies.
|
| 7.2 | ATTIC,
VENTILATION, ROOF VENTILATION, CEILING VENTILATION Comments: Inspected | |
| There is Passive Ventilation for air
to circulate in the attic. Passive Ventilation is any weather protected
opening in a roof system which allows air to circulate through the attic.
Ventilation helps keep the building cooler in the summer. The more ventilation the lower your utility bill will be for air conditioning. Heat radiates through the ceilings of any building and the less heat radiating the better. Types of vents for passive ventilation are stationary roof vents, screens at the eaves in the soffits, gable vents (as examples).
|
| 7.3 | ROOF
FRAMING, SHEATHING, CONDITION Comments: Inspected, Informational | ||
While I am in the attic I inspect the
roof framing and wood sheathing to determine if moisture has entered under
the roof covering or other locations. I try my best to access all
areas in the attic, but depending on how the building is designed
sometimes I cannot traverse to every location in the attic because of air
conditioning ducts blocking my travel or not enough head room, or the
floor framing is not visible to step on wood framing to traverse.
|
| 7.4 | BATHROOM
CEILING VENTILATION DUCTS, PLUMBING VENTS, DRYER VENT PIPES, FLUE PIPES,
SKYLIGHTS, SUPPORTS Comments: Inspected |
| I make every possible effort to look at all of the flexible and ridged ventilation duct(s) for bathroom-kitchen ventilation fan(s) and plastic-metal pipe(s) designed for venting sewage gas are terminated above the roof of the building as required. I did not see any obvious deficiencies today. |
| 7.5 | ATTIC
FAN, WHOLE HOUSE FAN Comments: Informational |
| Informational:
The attic does not have an (Click
Link) Electric Fan or (Click Link) Solar
Powered Attic Fan to remove hot attic air but I
certainly recommend you have one installed. They help keep the attic area
much cooler and allow the roof membrane under the tiles to last longer.
Attic Fans help keep the attic heat from radiating into the interior
ceilings, causing the Air Conditioning system to operate more than it
normally would without a thermostatically controlled power fan. Attics in
the desert regions of Arizona can reach temperatures over 150 degrees in
summer months.
Many new homes in the Phoenix area are now having Attic Fans installed because they lower your electrical rates. |
| 7.6 | MOISTURE
INTRUSION Comments: Inspected, Informational | ||
| Informational:
There are numerous locations I could see moisture stains on the roof
framing, associated with the current condition of the roof covering.
I am documenting there is moisture intrusion at several locations (as pictured). The condition of the roof covering has allowed moisture to enter the house at several locations.
|
|
Items |
| 8.0 | DOOR
BELL Comments: Inspected |
| The door bell operated today and is properly fastened to the exterior wall. |
| 8.1 | EXTERIOR
WALLS, MATERIAL TYPE, CONDITION Comments: Repair or Replace, Informational | ||||||
| There are gaps at
the Combustion Air Intake Grills at the east side of the Garage Wall
adjacent to where the Water Heater is located in the Garage. The Grills
should be replaced with a different type (Louvered Type recommended) which
does not allow rain water to enter but still allows air to flow into the
Garage for combustion air needed for the Water Heater to function
properly.
There are a couple locations the Cement Stucco is damaged at the front of the Garage, Stucco Patch is available at any Home Store to make the minor repairs to the damaged Stucco. A Handyman could make these repairs-upgrades for you. Informational: The exterior walls have a (Click) Cement Stucco finishing system installed, the wall system is built with Wood Framing, Styrofoam attached to the vertical wood framed lumber, a (Click) Weather Protective Barrier similar to Tyvek installed over the Styrofoam, (Click) Metal Lath is attached over the Styrofoam and Tyvek so the stucco is bonded-attached to the lath, with a two coat Cement Stucco finish applied. Cracks are common in Cement Stucco, unavoidable, common, typical of this type of exterior cladding.
|
| 8.2 | STUCCO
WEEP SCREED FLASHING Comments: Inspected, Informational |
| The Metal Weep Flashing at the very
bottom of the exterior Cement Stucco finished walls is installed correctly
where I could see it not covered with Landscaping Stone. The Metal Flashing is perforated so any water which might enter the walls from either cracks or holes in the Stucco has a way to exit the wall system without causing interior moisture damage. |
| 8.3 | EXTERIOR
DOORS, WEATHER STRIPPING, TRIM Comments: Repair or Replace | |
The Fire Rated
Door from the Garage into the Laundry Room needs a new Door Knob
installed. The components of the Door Knob are missing (receiver). A
Handyman could make the repair for you.
|
| 8.4 | SLIDING
GLASS DOOR(S) Comments: Inspected, Unsafe | |
The Sliding Glass
Door is required to have a Self-Closing Device present because there is a
Pool in the back yard. This is a law in Maricopa County and could save a
Child's life. We also highly recommend Pool Fences be installed at all
Pool properties, they are inexpensive.
|
| 8.5 | EXTERIOR
WINDOWS AND FLASHINGS, INTERIOR CONDITIONS NOTED Comments: Repair or Replace | ||||
| There are three
Dual Pane Glass Windows with the Rubber Seals between the window glass
shrunk from heat-sun-exposure. Two at the west side of the Kitchen and one
at the Second Floor Hall Bathroom above the Shower. You would need to have
a Glass Company remove the glass and replace it. The seals cannot be just
repaired, they are Factory Sealed with (Click
Link) Argon
Gas and (Click
Link) Desiccate to eliminated condensation from forming between the dual
panes of glass.
Informational: I did not see an condensation between the dual panes, the seals will shrink and still may not allow the gas to escape in many instances, but expect the (More information-Click) Argon or Krypton Gas to escape in the future. Also at the west side kitchen windows the Vinyl Trim has also shrunk from heat-sun exposure, clear Silicone Caulk should be applied in the gap(s), or have the Trim replaced with new Vinyl Trim, any residential Glass Company could make the repairs for you.
|
| 8.6 | DIVERTER-KICK OUT FLASHING ILLUSTRATION,
INFORMATION Comments: Inspected |
| The Kick-Out Diverter Flashings at wall-roof corners are installed correctly. |
| 8.7 | SOFFITS,
FASCIA, EAVES, TRIM Comments: Inspected, Informational | ||
The eaves are
stucco finished, there was no immediate concerns. Exterior wood trim was
in normal condition for the age of the house, but should be painted to
prevent any future deterioration.
|
| 8.8 | DECKS,
BALCONIES, RAISED DECKS, STEPS, RAILINGS Comments: Repair or Replace | ||
| The Epoxy Coating
at the Deck Floor needs to be refinished. There are numerous surface
cracks allowing water to damage the Sheetrock Ceiling below. Contact a
company which specializes in refinishing exterior coatings. (Click Link) Quality Epoxy is a
local company I have personally hired in the past to perform work at my
house, I recommend them. Their work was both professional and
affordable.
Informational: The Rear Deck was in normal condition for safety. The Parapet Wall around the Deck outer perimeter edge was the correct height for a Guardrail System.
|
| 8.9 | EXTERIOR
CEILINGS, FRAMING, EXTERIOR SHEETROCK Comments: Repair or Replace | ||||
The rear Patio
Ceiling is water damaged because of the condition of the (Click Link) Rear Deck Epoxy Finished Floor above which is cracking at various locations as previously
mentioned. You will need to have the floor refinished before repairing the
water damaged Sheetrock Ceiling at the rear patio.
|
| 8.10 | EXTERIOR
ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected, Informational | ||
| Informational: All Exterior &
Garage Receptacles are (Click link) Ground
Fault Circuit Interrupters "GFCI's". The "Reset Button" to reset the
electrical current to the receptacles if one ever Tripped-Disconnected
Electricity is in the Second Floor Hall Bathroom on the west wall (as
pictured).
Exterior Lighting operated when inspected, lights with burnt or missing bulbs did have electricity to the fixture when I tested fixtures with burnt bulbs.
|
![]() |
![]() |
![]() |
![]() |
|
Items |
| 9.0 | FLOORS Comments: Inspected |
| The floor coverings are serving their purpose to cover the concrete slab under them. Licensed Arizona Home Inspectors do not report on the condition of Floor Coverings, everyone has their own opinion (please click link for Arizona Home Inspection Laws ) for more information. |
| 9.1 | WALLS,
CEILINGS Comments: Repair or Replace | ||||||||
There is water
damage in the Living Room at the southwest ceiling and west wall below a
window. I believe the water damage is associated with the Roll Roofing
Material on the roof above with cracks in the material and the inability
for water to drain from the roof at this location from the Tiles installed
tight to the exterior wall and debris blocking drainage. Water is getting
into the wall and running downward around the first floor living room
window and existing on the floor. The roof should be repaired before the
damaged sheetrock is repaired-replaced.
|
| 9.2 | WALL
CABINETS Comments: Inspected |
| There was no concern present with any Wall Cabinet in the house. |
| 9.3 | INTERIOR
TRIM, BASEBOARD Comments: Inspected |
| The condition was normal where it is not behind furniture and personal items (visible). |
| 9.4 | INTERIOR
DOORS, KNOBS, HARDWARE Comments: Inspected |
| Interior doors were inspected. They operated and latched properly at the time of this inspection. |
| 9.5 | CLOSETS,
DOORS, SHELVES Comments: Inspected |
| The closet doors functioned correctly today. |
| 9.6 | MASTER
BEDROOM CLOSET Comments: Inspected |
| There was no concern present with the Master Closet. |
| 9.7 | INTERIOR
AND EXTERIOR STEPS AND STAIRWAYS, GUARDRAILS, HANDRAILS Comments: Inspected |
| Interior stairway was constructed to current building standards, no concerns were present. |
| 9.8 | ELECTRICAL WIRING, OUTLETS, SWITCHES, AND
LIGHTING Comments: Inspected |
| I tested the accessible Electrical Receptacles and Switches, no concern was present regarding having electrical current to them at the time of this inspection. Fixture(s) with Burnt Bulbs had electricity to them as well. |
| 9.9 | CEILING
FANS Comments: Inspected | ||||||
Ceiling fans
functioned properly when tested, the south Fan at the second floor Hallway
is noisy, but functional.
|
| 9.10 | SMOKE
DETECTORS, CARBON MONOXIDE DETECTORS Comments: Repair or Replace, Informational |
| The smoke detectors need the batteries changed yearly. When you close escrow, I suggest replacing the Smoke Detectors with Smoke-Carbon Monoxide Detectors for your safety. |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|
Items |
| 10.0 | TUB
SHOWER UNIT(S) Comments: Repair or Replace, Informational | ||||
The Tub-Showers
drain slow, you should have the drain traps professionally cleaned, hair
and debris collects. Have a Licensed Plumber professionally clean all the
drain traps at all Bathroom Fixtures (normal maintenance).
|
| 10.1 | MASTER
BATH TUB OR JETTED TUB Comments: Inspected | ||
This fixture was in normal
condition and functioned properly at the time of this inspection. There
was no leakage at the Water Control Valves(s), the fixture drained
correctly today.
|
| 10.2 | WALK-IN
SHOWER(S) Comments: Inspected, Informational | ||
| The fixture operated correctly
today. There was no water leaking from the water supply diverter valve(s),
the shower drained correctly after running water for several minutes. The
water temperature dropped significantly after running heated water for an
extended period of time.
The tenant said he has to clean the drain periodically, all the drain traps in the Bathrooms should be professionally cleaned by a Plumber. There is Mildew forming at the Shower Surround Components which could be cleaned with basic household cleaning products (normal maintenance).
|
| 10.3 | TOILETS Comments: Repair or Replace | |||
The Flush Handle
is missing at the Master Bathroom Toilet. The Toilet in the second floor
Hall Bathroom is not attached to the floor, a new Wax Seal Kit is needed.
Have a Plumber make the necessary repairs.
|
| 10.4 | SINKS,
COUNTERTOPS, CABINETS Comments: Inspected, Unsafe, Informational | ||||||||
| The sinks and cabinets are functional
in bathrooms. I filled all Sinks several times with water, allowed the
water to drain several times. There were no active leaks at any portion of
the fixtures.
(Read this link for more information) The water temperature was over 135 degrees which is considered excessive, you should have the Water Heater turned down below 120 degrees so nobody could experience burns to the skin, especially children-infants.
|
| 10.5 | DRAINAGE
PIPES Comments: Inspected, Informational | ||
There were no active leaks at any
drainage pipes at the time of this inspection. You should check for leaks
after the current owner(s) vacate the property. Many times drain pipes are
accidentally bumped when removing personal belongings, which could cause
leakage. Run water at each Sink and look for possible leaks before placing
your personal items in the Vanities.
|
| 10.6 | WATER
VALVES AND SUPPLY LINES Comments: Repair or Replace, Informational | ||
| There were no
active leaks at the time of this inspection. I do recommend replacing the
old Gate Valves with new Ball Valves with New Reinforced Woven Metal Water
Supply Lines to every Fixture in the house.
If you turn one of these old valves 9 times out of 10 they will break or begin to leak possibly causing major water damage to your home before the water can be turned off at the Main Water Valve outside or the Valve and the City Meter usually located behind the curb in the front yard. New Ball Valves and Reinforced Supply Lines at every fixture is not that expensive compared to repairing water damage caused by a $6.00 Valve or $5.00 Supply Line to a fixture failing (especially when nobody is home).
|
| 10.7 | WATER
PRESSURE, AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected, Informational |
| The water pressure in the bathrooms was normal. Some drains emptied slow, all the Fixtures should have the Drain Traps and Drain Stop Assemblies cleaned by a Plumber (normal maintenance deferred). |
| 10.8 | TOWEL
HOLDERS & HAND DRYERS Comments: Inspected |
| There was no concern present today. Towels were placed on Towel Bars at the time of this inspection. I did not see any obvious concerns, such as loose, or bent Metal Towel Holders |
| 10.9 | ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS,
LIGHTING Comments: Inspected, Informational |
| Ground fault circuit
interrupters were tested in bathroom(s), no concerns were present.
The lighting functioned properly.
Informational: The Reset GFCI Receptacle for all Bathrooms is at the Second Floor Hall Bathroom. |
| 10.10 | CEILING
EXHAUST VENTILATION Comments: Inspected |
| Bathroom ceiling ventilation fans were functional, vent piping is installed through the attic, terminated above the roof as required. |
| 10.11 | BATHROOM
WINDOWS Comments: Inspected, Informational |
| There was no concern with any operational windows in the Bathrooms which can be opened to remove excessive moisture while the Shower is operating. |
| 10.12 | MIRRORS Comments: Inspected |
| There was no concerns with the Mirrors above Sink Vanities in the Bathrooms. |
| 10.13 | MEDICINE
CABINETS Comments: Inspected |
| There was no concern present with the Medicine Cabinets in the Bathrooms. |
|
Items |
| 11.0 | KITCHEN
CABINETS AND COUNTERTOPS Comments: Inspected | |
Cabinets and Countertops are in normal
condition for a home which has been lived in. I report repairs which are
needed by a Licensed Contractor not cosmetic items.
|
| 11.1 | KITCHEN
ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected, Informational |
| Ground fault circuit interrupters were tested. Lighting functioned correctly. The Reset button for the GFCI Receptacles is at the right side of the sink and at the east wall next to the Range-Oven for your information. |
| 11.2 | KITCHEN
SINK AND FAUCET Comments: Inspected | ||
The Faucet operated correctly and the
Sink is in normal condition.
|
| 11.3 | SINK
DRAINAGE PIPES Comments: Inspected | ||
There were no active leaks at the time
of this inspection.
|
| 11.4 | SINK
WATER VALVE AND SUPPLY PIPING Comments: Inspected | ||
| There were no leaks at the time of
this inspection. But the older Gate Valves should be replaced with new
Ball Valves (normal maintenance)
Informational: Older Gate Valves may fail or not stop water when necessary if a leak occurs at a fixture in the house. We always recommend you have older Gate Valves upgraded to new reliable Ball Valves with Woven Metal Reinforced Water Supply Lines from Valves to Fixtures. This is an upgrade all older homes should have, the cost is insignificant compared to water damage that could occur if an older Gate Valve or Supply Line failed.
|
| 11.5 | FOOD
DISPOSER Comments: Inspected |
| Disposer functioned properly. Electrical and plumbing connections were consistent with current standards. |
| 11.6 | WATER
PRESSURE AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected |
| The water pressure was acceptable and drains emptied correctly. |
| 11.7 | DISHWASHER Comments: Inspected, Not Tested, Informational | ||
The appliance was full of clean
Dishes. I asked the tenant if the appliance functioned, she said there was
no concerns. The drainage pipe is properly supported above the base of the
sinks to help prevent cross-contamination of waste water flowing back into
the appliance.
|
| 11.8 | RANGE AND
OVEN Comments: Inspected, Informational | |||
Range and Oven are 240 volt
electric. The appliance functioned today. I used a Thermal
Imaging Camera to confirm the heating elements were functional
today.
|
| 11.9 | RANGE
VENTILATION Comments: Inspected, Informational | |
The Microwave Range Vent is terminated
to the exterior of the house. The metal filtering screens at the bottom of
the Microwave need to be cleaned with hot water and soap periodically,
cooking grease builds up in the filtering system.
|
| 11.10 | MICROWAVE Comments: Inspected, Informational | ||
Microwave was tested to heat a wet
paper towel. I do not know if the automatic programming devices in the
appliance function properly, I only test the appliance to determine if in
fact it heats an object.
|
| 11.11 | REFRIGERATOR-FREEZER Comments: Inspected, Informational | ||
| The Refrigerator-Freezer was
functioning today. Refrigerators-Freezers are beyond the scope of a
building inspection but I do look at the appliance as a courtesy.
If there is a water supply to the appliance I do not move the appliance to determine the condition or installation methods, the floor could become damaged.
|
| 11.12 | RECALLED
APPLIANCES Comments: Informational |
| We do not research whether an
Appliance has been Recalled by the Consumer
Product Safety Commission, but we do recommend you research all the
Appliances in the house. We are performing a visual Inspection Only. You
would need to document all the Model & Serial Numbers of each
Appliance and goto the CPSC Website linked above to determine if any
Appliances in the home need to be repaired or replaced, we test for normal
operation only but provide this information as a courtesy. There is an
incredible amount of appliances with Recalls.
Any Appliance which is not permanently built-in we are not required to inspect it according to the laws of the state of Arizona, but we do document any obvious defects if they are visible, Dishwashers, Ovens-Ranges, Microwaves, Refrigerators, etc, are not permanently built-in Appliances but are operated using normal controls as a courtesy. You can also check here. |
|
Items |
| 12.0 | PLUMBING
CONNECTIONS FOR WASHER Comments: Inspected, Informational | ||
Plumbing
connections for a washer are present, but I recommend upgrading the old
Gate Valves to new Ball Valves. Generally older Gate Valves will not
completely stop water when turned off from mineral deposits in the Valves.
They usually begin to leak water at the Valve Stems or may Break if
operated because the valves are not exercised on a regular
basis.
|
| 12.1 | WASHER
DRAINAGE PIPE Comments: Not Tested, Informational |
| I do not operate Washing Machines but I did not see any obvious concerns or evidence water overflowed in the past at the drain assembly behind the appliance at the wall. |
| 12.2 | WASHER-DRYER, ELECTRICAL OR GAS AVAILABLE (ENERGY
SOURCE) Comments: Inspected, Not Tested |
| The energy source available to operate a washer and dryer is 120/240 Volt electricity or Natural Gas, the Receptacles were tested today, there was no concern present. The Dryer in the house now is Electric, not Gas, the Gas Valve is capped off properly. |
| 12.3 | OVERFLOW-DRAIN PAN Comments: Informational |
| I always recommend a Overflow Drip Pan be installed under all Washing Machines in the event a leak ever occurred, they are inexpensive compared to what water damage costs to repair. |
| 12.4 | DRYER
VENTING Comments: Repair or Replace, Unsafe, Informational | ||
| The Dryer Vent
Pipe is installed through the attic and terminates above the roof. I
recommend having the vent professionally cleaned-vacuumed before you
connect a Dryer to the Vent Pipe, the Vent is plugged with lint. The vent
should be vacuumed now and annually by a qualified professional. Lint
build-up can create a fire hazard and impedes the performance of your
appliance.
If you do not know a Licensed Contractor I recommend Vince Divarco at Ductz 623.412.2555. Many of my past clients have used his company and I have never heard any complaints.
|
| 12.5 | ELECTRICAL OUTLETS, SWITCHES, GROUND FAULT CIRCUITS,
LIGHTING Comments: Inspected, Informational |
| Electrical Receptacles and Switches were tested, no concern was present today. The Reset Button for the Ground Fault Protected Receptacles is in the second floor Hall Bathroom. |
| 12.6 | ROOM
EXHAUST VENTILATION Comments: Inspected |
| Laundry room has a Ceiling Ventilation Fan vented to the exterior of the home which functioned correctly today. |
![]() |
![]() |
|
Items |
| 13.0 | WALLS,
CEILINGS Comments: Repair or Replace | ||||||
| There is excessive
moisture damage to the sheetrock ceiling in the garage, the leak above the
Two Car Door Opener was wet today from the past storm. The second wet
location above the Water Heater is caused from the Toilet not being
properly attached to the floor. The Wax Seal needs to be replaced by a
Licensed Plumber.
Have a Plumber install a new Wax Seal Kit before you hire a Licensed Contractor to replace the Sheetrock Ceiling in the Garage. The roof needs to be repaired above the Garage as previously noted before repairs are made to the Garage Interior also.
|
| 13.1 | FLOOR Comments: Inspected, Not Tested, Informational | ||
Minor cracks in concrete are normal
(typical). I could only see the floor at a couple of locations (heavily
occupied).
|
| 13.2 | PASSAGE
DOOR TO INTERIOR/EXTERIOR Comments: Informational |
| Passage door from the Garage to the Interior is Fire-Rated, which is a current and past building standard. |
| 13.3 | GARAGE
DOOR MATERIAL, CONDITION Comments: Inspected |
| Garage doors are metal, the condition was acceptable. |
| 13.4 | GARAGE
DOOR OPERATING TRACKS AND DOOR ROLLERS, CONNECTIONS Comments: Repair or Replace | ||
The Door Tracks
need to be adjusted at the One Car Door, the Door sticks at joints in the
Track System when opening-closing from mis-alignment. Have a Garage Door
Specialist adjust the Door Tracks properly.
|
| 13.5 | GARAGE
DOOR OPENER(s) Comments: Repair or Replace | ||
| The Chain Drive
needs to be tightened, it is hanging downward considerably. If not
repaired soon the Chain will catch on the opener drive mechanism and break
either the Chain or the Door itself where the arm from the Door Opener is
attached to the Door. Have a Garage Door
Specialist make the repairs.
The Automatic Door Opener functioned properly when met with reasonable resistance (reversed), photo-electric eyes are present and operational so the door will reverse if someone walks under the door while it is closing (required on all garage doors since 1993). There is no Door Opener for the Single Car Garage Door.
|
| 13.6 | GARAGE
DOOR TRIM, WEATHER STRIPPING Comments: Inspected, Informational |
| There was no concern with the exterior vinyl and wood door trim around both Garage Doors. |
| 13.7 | ELECTRICAL RECEPTACLES, LIGHTING Comments: Inspected, Informational |
| Ground Fault Circuit Interrupters (Click link) (GFCI)
functioned correctly, lighting and switches were operational.
Informational: The Reset button for the Garage & Exterior GFCI Protected Receptacle is in the Second Floor Hall Bathroom. |
![]() |
![]() |
![]() |
![]() |
|
Items |
| 14.0 | POOL,
GENERAL INFORMATION Comments: Inspected, Informational | |
| The overall condition of the Pool was
normal for the age. I look at the electrical equipment and make sure the
GFCI functions, the motor(s) are grounded-bonded, and make sure there are
no obvious leaks in the visible portion of the Pool Piping above ground at
the equipment.
I do not Dye Test for leaks nor test water for correct chemical balance, only a (Click Link) Licensed Pool Technician should perform these tasks. All Pools need to be Serviced by a Pool Technician yearly, I recommend you have the entire system Serviced now. Any repairs listed below or other repairs the Pool Technician may find while servicing the Pool and Equipment should be repaired before your inspection contingency period ends by a Licensed Contractor.
|
| 14.1 | POOL
WEBSITE INFORMATION Comments: Informational |
| Everything there is to know about a Pool is available at this website, Click Link. You should read all the important information about a Pool, even if you have owned a house with a Pool in the past I believe you will find some interesting, important, and safety related material at this link. |
| 14.2 | POOL
FENCE Comments: Not Tested, Informational |
| I highly recommend having a Pool Fence be installed, the cost is insignificant compared to a Child Drowning. The drowning rate is incredibly high in Maricopa County. All Gates-Doors to the rear yard are required by law to have Self Closing Devices installed and operational as well. |
| 14.3 | POOL
DECK, CONDITION Comments: Repair or Replace | ||
There is
deterioration of the decking at the north side of the pool at the edge,
west of the waterfall. A pool company could make the repair for you. This
should be repaired before your inspection contingency period ends by a
Licensed Contractor.
|
| 14.4 | SURFACE
FINISH, TYPE, CONDITION Comments: Inspected |
| The Pool has a (Click link) Pebble Tec Finish, which is better than Plaster in my professional opinion, Pebble Tec Finishes do not deteriorate like a Cement Plaster Finish will. The Pool is full of water but I did not see any obvious concerns with the finish. Brushing the surface weekly will help keep the water clean, or have a (Click link) Pool Service Company take care of the system for you. |
| 14.5 | TILE
EDGE Comments: Inspected | ||
I did not see any concerns with the
Tiles at the top portion of the Pool finish or at the Water
Feature.
|
| 14.6 | CLEANING
PUMP Comments: Inspected |
| The Cleaning Pump operated when I manually turned the Timer on, the Pool Sweep immediately began to move along the bottom of the pool, there were no active leaks at piping. The Pump is bonded to the electrical grounding system. |
| 14.7 | ABOVE
GROUND PIPING, VALVES, LEAKS, CONDITION Comments: Inspected | ||
There were no visible leaks at any
Pipe, Valve, Filter, Fittings, above the surface of the soil today.
|
| 14.8 | BOTTOM
SUCTION SCREEN PROTECTOR Comments: Unsafe, Informational | ||
There should be
Raised Plastic Screen Protectors installed at the bottom suction screens
(Click) (Anti-Vortex) so a child-adult cannot get their hair-clothing caught in
the screen should the pump be operating when someone is in the Pool. A
Pool Service Technician could install an Anti-Vortex Screen Protector for
you (safety item).
|
| 14.9 | POOL
SWEEP, CONDITION Comments: Inspected | |
The Pool Sweep was operating-moving
when I turned the Cleaning System on at the Timer, I do not judge the
cleaning ability of the system but I do note it was operating today. Pool
Sweeps need periodic maintenance like any other mechanical device, you
should ask the current owner if any repairs-upgrades were made to the
Cleaning System since she has owned the home.
|
| 14.10 | SKIMMER
BASKETS, PUMP COLLECTION BASKETS Comments: Inspected, Informational | ||
The Collection Basket at the Skimmer
located at the side of the pool (east) and the Collection Basket at the
Cleaning Pump need to be cleaned of debris frequently. The Skimmer Basket
needs to be cleaned daily, the Basket at the Pump should be cleaned
weekly, or as necessary depending on weather conditions, excessive foliage
in the water. You may consider having a (Click
link) Pool Service Company
maintain the Pool for you, most work for reasonable rates, they check
chemical balance, backwash Filters, and clean Collection Baskets.
|
| 14.11 | FILTER,
TYPE, CONDITION Comments: Inspected, Informational | ||
Click the link for a wealth of
information. The Filter is
a Sand Media Type, I suggest asking the current owner when the Filter
was serviced by a Pool Service Technician, it is important to have the
entire system serviced yearly.
|
| 14.12 | FILTER
AIR RELIEF VALVE Comments: Inspected, Informational | ||
| There was no water leaking from the
Air Relief Valve at the top of the Filter. This Air Relief Valve is
necessary to use when the collection basket at the Pump is cleaned of
debris, air gets into the Filter Tank. The Filter needs the air removed
for proper functionality of the filtering-cleaning system.
You should read about the system-equipment before operating any devices or have a Pool Service Company service the entire system for you weekly. The cost is relatively low to have a Professional service the Pool and Equipment. (Click link) Poolman is a recommended licensed contractor in Arizona, they service many Pools throughout the valley which is why they offer low prices. I have never had any issues using their service myself.
|
| 14.13 | CHEMICAL
NEEDS, CONDITIONS, RECOMMENDATIONS Comments: Not Tested, Informational |
| You should have
the water tested for the proper chemical balance, I suggest you ask the
current owner before you close escrow if a Pool Service Company takes care
of the Pool Water chemical needs. If not, you can take a water sample to
any Pool store such as Leslie Pools, Paddock Pools, they test water free
of charge and tell you what if any chemicals maybe needed to stabilize the
water at proper levels.
You may consider having a Pool Service Company like (Click) Poolman take care of the system for you, they service Pools and Equipment at affordable rates. |
| 14.14 | TIMER,
ELECTRICAL EQUIPMENT, GROUNDING, GFCI PROTECTION Comments: Inspected, Informational | |||
The Ground Fault Circuit Interrupter
operated correctly when I intentionally created a Fault, the receptacle
disconnected electricity as designed. The Grounded Conductor is terminated
to the metal post the Timer is attached to, the Pump is bonded properly,
no visual concerns were present.
|
| 14.15 | POOL
LIGHT(S), SPA LIGHT(S) Comments: Repair or Replace | ||
The Pool Light
would not operate using the switch at the electrical equipment, have a
Pool Technician make the repair.
|
| 14.16 | WATERFALL, WATER FEATURES, NEGATIVE
EDGE-WATERFALL Comments: Inspected | ||
The Water Feature was functional at
the time of this inspection. I did not see any leaks in back of the Water
Feature either.
|
| 14.17 | WATER
AERATOR Comments: Repair or Replace, Not Tested | ||
| The Operating
Handle for the Water Aerator is broken at the pool piping-valves, you
would need to have a new Ball Valve installed if you want to operate the
Water Aerator.
Plastic Valves and Piping exposed to the sun deteriorates the material. It would be in your best interest to have a shade screen cover manufactured by a company like Arizona Sun Screen to protect the piping and equipment from direct sun exposure. The Screens are easily removable to service the equipment.
|
| 14.18 | WATER
AUTO-FILL VALVE, CONDITION Comments: Inspected | ||
There is an automatic water filler for
the Pool located in the pool deck. I do not know for a fact it keeps the
water in the pool at a constant level which it's designed to accomplish,
someone would need to be living in the home or monitoring the water level
daily to determine if the water stays the correct level in the Pool. The
sun evaporates water rapidly in the desert regions of Arizona.
|
|
Items |
| 15.0 | TRUSTWORTHY LICENSED CONTRACTORS AND SERVICE
PROVIDERS Comments: Informational |
|
ANY ITEMS IN THE REPORT WHICH NEED TO BE REPAIRED OR REPLACED HAVE A LICENSED CONTRACTOR DO THE WORK (Click link please) The Licensed Contractors and Service Providers
listed below are people I have had personal experience working with, or
they have worked for my past clients, they are trustworthy professionals
who do not take advantage of their clients. Handyman All In One Home Repairs - Jim Bourassa
http://www.allinonerepairs.com/
480.607.9556 Solar Panel Repair Replacement: Anthony Iannucci 480.941.7461 or 480.390.4822 Stucco Repairs, any type: Richard Causey:
480.603.5705 Locksmith Ace Lock-N-Key David Kamber: 480.747.8298 Appliance Repair-All Makes Models, Honest
Company Pool Service-Repair: Cris Hands 602.799.5368 (Click) Poolman: Affordable Service, Honest Licensed Contractor. Licensed Contractor, Additions, Remodeling, Custom Homes: Greg Woolf: 480.540.1710 Carpet Cleaning: (click) Carpet Cleaning: F&F Restoration 480.314.4800 Window Repair or Replacement, Licensed Contractor: (click link) Panoramic Window & Screen 602.695.3226 Plumbers, Licensed (click link ) Drain Pro Drain Video Scanning, Repairs: 1.800.380.7385 Polybutylene (PB 2110) Replacement Plumbers, Peerless Plumbing: 602.265.5508 Electrical Repairs (click link) America's Best Electric Nick Cordova: 480.703.9598 Heat & Cooling, Dave Barraco, Calendar Air Conditioning: 602.332.0363 Roofing, New, Repairs, Tiles, Shingles (click link) Phillips Roofing : 623.873.1626 Foam Roof Coating, Tile, Shingle, (click link) Durafoam Roofing LLC. 480.941.5373 Professional Duct Cleaning, (click link for coupon) Dutz of Phoenix : 623.466.8625 Mold Testing, Dylan Bucknivich: 480.510.5865 Termite Inspection-Treatment Strikeforce Pest & Termite: 480.922.8800 Garage Doors & Openers (click link) Heritage Garage Door and Repair. Insulation Needs, All Types: (click link) Mesa Insulation Chimney Sweep: (Click link) Adirondack Chimney Sweep Sun Screens: (click link) Arizona Sun Screen , Window Screens, Sun Screens. I do not receive ANY compensation for referring the contractors listed above, they are simply the only Trustworthy Licensed Contractors I know, but you should always get at least three quotes from Licensed Contractors before hiring anyone. |

10599 E. Betony Dr.
Scottsdale, AZ. 85255
AZ License
43396
Customer
Sample Report
Address
876 Palm Tree Dr.
Scottsdale AZ
85254
| 1. GENERAL BUILDING AND SITE INFORMATION | ||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||
3. ROOF, MATERIALS, TYPE,
CONDITION | |||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||
4. AIR CONDITIONING, COOLING AND HEATING
EQUIPMENT | ||||||||||||||||||
| ||||||||||||||||||
5. ELECTRICAL SYSTEM, SERVICE EQUIPMENT,
SUB PANELS | |||||||||
| |||||||||
6. PLUMBING, SYSTEMS,
COMPONENTS | |||||||||
| |||||||||
7. ATTIC, INSULATION, AND
VENTILATION | |||||||||
| |||||||||
8. EXTERIOR OF BUILDING, MATERIALS
INSTALLED AND CONDITION | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||
9. INTERIOR OF THE ENTIRE
BUILDING | ||||||||||||||||||
| ||||||||||||||||||
10. BATHROOMS, FIXTURES, PLUMBING
CONECTIONS | |||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||
12. LAUNDRY ROOM, WASHER PLUMBING, DRYER
VENTING | |||||||||
| |||||||||
13. GARAGE, DOORS,
AUTO-OPENERS | |||||||||||||||||||||||||||
| |||||||||||||||||||||||||||
14. POOL, SPA, EQUIPMENT,
CONDITION | ||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||
15. REPORT CONCLUSION | |||||||||
| |||||||||
There should be at 6-8 inches of free clearance from the base of the exterior walls to final grade with the soil sloped 1/4 inch per foot away from the foundation.
I highly recommend you have a qualified landscaper grade the soil around the home properly so water flows away from the foundation and toward the street.