| Date: 2/18/2006 | Time: 08:55 AM | Report ID: 2.18.06 |
| Property: 2150 W. Southern Ave. Phoenix, AZ. 85008 |
Customer: Patrick Wagner |
Real Estate Professional: Commercial Property Realtors |
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor or professional.
Inspected: This term means I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing normal wear and tear. The notation does not mean that the item is perfect but does meet a reasonable standard on the day of inspection.
Repair or Replace: The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Requires Immediate Attention: The item, component or unit needs immediate attention by a qualified professional or contractor for the safety or health of the occupants of the building. Could cause further major deterioration, or complete failure of a system or component. Worsen appreciably, cause damage, or be a serious hazard.
Unsafe: A condition in a readily accessible, installed system or component which is judged to be a significant risk of personal injury during normal day to day use. The risk may be due to damage, deterioration, improper installation or a change in adopted construction standards.
Not Tested: I did inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not testing or operating.
IMPORTANT NOTICE TO THIRD PARTIES: Receipt of this report by anyone other than the above listed party(s) is not authorized by Inspect Arizona Companies, Inc. This report is prepared for the sole and exclusive use for the client who signed the INSPECTION AGREEMENT and is subject to the terms and conditions agreed upon. This Inspection Report is a product, and is copyrighted by Inspect Arizona Companies, Inc. at the date of this inspection. Duplication by any means whatsoever is prohibited without prior written permission and authorization from Inspect Arizona Companies, Inc. Unauthorized duplication, use, or reliance of this report shall constitute all parties agreed upon to hold harmless, whether individual, joint or otherwise, Dale Duffy and Inspect Arizona Companies, Inc., their successor's and assignee's.
PERMITS/BUILDING CODE VIOLATIONS: If you are concerned about code violations or building permit information you should: 1) Contract with our company to research permit information available at the appropriate building and safety office, 2) If you have additional concerns with regard to code violations you may contract for a code compliance survey of the property.
You have contracted with us to perform a commercial inspection in accordance with Arizona industry standards for the inspection profession. This is different from our technically exhaustive inspection which takes several days to complete, involves the use of specialized instruments, the dismantling of equipment, video scanning, destructive testing and laboratory analysis of possible contaminates. Our purpose is to identify defects or adverse conditions that need additional evaluation, are safety concerns or may lead to costs that would significantly affect your evaluation of the property at the time of this inspection.
Client Is Present: Yes | Building Faces: East | Weather: Clear |
Temperature: Over 65 degrees | Rain in last 3 days: Yes |
Inspection Items
|
| 1.0 | BASIC REPORT INFORMATION OR BUILDING CHARACTERISTICS Comments: Inspected |
| The current tenants were in the process of moving out today. I
inspected all locations I could access where personal belongings
were not piled. The most expensive repair in my opinion will be to repair all the settlement and shrinkage cracks in the sheetrock walls at the interior of the building. The roof repairs at the flat portion in my opinion as a past commercial builder should range from |
| 1.1 | GENERAL EXTERIOR SITE DRAINAGE Comments: Repair or Replace | ||||
| When the building was constructed the grade of the lot and
walkways at the south, east and west side of the building should
have been lower than they currently are (as built).
There is negative drainage at these areas next to the foundation
of the building, and the final grade (landscape rock) is too close
to the bottom of the exterior finished wall and should be lowered
as much as possible while still allowing the grade to slope so
rain water drains away from the foundation. A contractor can add pipe and fittings to make this needed upgrade.
|
| 1.2 | TREE OR VEGETATION NEXT TO THE BUILDING Comments: Repair or Replace |
| I recommend trimming any tree branches in direct contact with the building. The wind moving the branches will cause damage to building components (roof , fascia, stucco). |
| 1.3 | DRIVEWAY, PARKING LOT, WALKWAYS, PATIOS, ENTRYWAYS, CONDITION Comments: Inspected |
| The exterior hard surfaces were in normal condition at the time of this inspection. Minor cracks in concrete are normal, considered typical. |
| 1.4 | IRRIGATION PIPING Comments: Repair or Replace | ||
| I do not know if the building association is responsible for the
irrigation system or you are, but there are numerous heads missing
from the drip irrigation 1/4 inch lines to the different plants and
bushes.
Regardless of who is responsible for the system I recommend a licensed landscape professional look at all the irrigation lines to the vegetation and make the necessary repairs needed.
|
Inspection Items
|
| 2.0 | FOUNDATION TYPE; CONDITION Comments: Inspected, Not Tested |
| The foundation of this building is poured concrete, no major
concerns were visible at the time of inspection (where I could
actually see it, landscape rock is to high).
Minor cracks are common in concrete products and the condition of this foundation is considered typical where I can actually see the concrete. |
| 2.1 | FLOOR TYPE; CONDITION Comments: Inspected |
| Floors in the building are constructed of poured concrete. The
conditions are acceptable with regard to the structural integrity of
the concrete slab on grade floor system.
There are floor coverings present except in the back room of the building where I can see expansion joints, which is probably why the tiles are cracked at the front of the building, concrete expands and contracts, which causes the tiles to crack, if there was differential movement up and down it would be a issue, but I did not see any. There was no visual evidence of Major Wall Cracks at the Floor Level which would tell me a concern is present. |
| 2.2 | EXTERIOR AND INTERIOR LOAD BEARING WALLS; TYPE; CONDITION Comments: Inspected |
| The exterior and interior walls are constructed with wood and steel framing materials, the walls are covered with sheetrock at the interior. There was no visible concern with the wall framing structurally. |
| 2.3 | CEILING MATERIAL; TYPE; CONDITION Comments: Inspected |
| Ceilings in the building were constructed with a Drop Panel System. The condition was acceptable, no concerns were present today. |
| 2.4 | ROOF STRUCTURE TYPE; CONDITION Comments: Inspected |
| The roof structure of this building is constructed with engineered wood trusses & rafters with oriented strand board (OSB) attached to the trusses for roof sheathing. Visually inspecting the condition of the components above the ceilings there was no concern where access could be gained. |
| 2.5 | POSTS, BEAMS, COLUMNS TYPE; CONDITION Comments: Inspected |
| The load bearing beams I could see above the ceiling tiles are in normal condition, at the front of the building there is also large wood beams, no concern was present there either. |
Inspection Items
|
| 3.0 | EXTERIOR WALLS, CONDITION Comments: Repair or Replace | |||
| The building has an exterior insulated finish system, commonly
know as stucco. Buildings in Arizona experience extreme heat in
the summer and sometimes rather cold conditions in the winter,
which cause the building materials to expand and contract.
Stucco will exhibit cracks in the finish from these conditions which cannot be stopped. When cracks become wide enough for rain water to enter in back of the finish, caulk should be applied to the cracks and touched up with paint. Cracks in stucco are not considered unusual, and are found on all buildings. I recommend a licensed contractor go around the building and caulk all the cracks with a good quality paintable caulk and touch up the repairs with new paint before you close escrow.
|
| 3.1 | STUCCO WEEP SCREED FLASHING Comments: Inspected |
| The weep flashing at the bottom of the exterior stucco walls is installed correctly. |
| 3.2 | BRICK, ROCK, VENEER Comments: Inspected |
| The rock veneer is in normal condition. |
| 3.3 | SOFFITS, FASCIA, EAVES, TRIM Comments: Inspected |
| The exterior trim, fascia, and eaves on this building are in normal condition. |
| 3.4 | EXTERIOR WINDOWS AND FLASHINGS, INTERIOR CONDITIONS NOTED Comments: Inspected |
| Windows are commercial grade glass. The conditions were good at the time of this inspection. |
| 3.5 | WINDOW FRAMES Comments: Repair or Replace |
| The window frames should be caulked at the exterior where they meet the stucco, some cracks are excessive from shrinkage and settlement but need repair. |
| 3.6 | EXTERIOR DOORS AND WEATHER STRIPPING Comments: Inspected |
| The exterior entrance doors operated and latched correctly when inspected. The weather stripping was functional. |
| 3.7 | EXTERIOR ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Exterior outlets are Ground fault circuit interrupters, there was no concern present. The exterior lights functioned correctly also. |
| 3.8 | EXTERIOR PLUMBING, FAUCETS Comments: Repair or Replace | |
The hose faucets functioned correctly, but the stucco needs to be
caulked around the one at the rear of the building.
|
![]() | ![]() | ![]() |
Inspection Items
|
| 4.0 | ROOF COVERINGS, TYPE, CONDITION Comments: Repair or Replace | |||||||||
| The roof system was inspected by walking the flat portions and I
used a ladder to inspect the clay tile areas, there was no
concern with the clay tiles, but the east side (front) of the building
needs the flat roof portion sealed with a Reflective Roof Coating.
This portion of the roof is also holding rain water at the northeast portion by the roof drain. When the roof was built, there is a low spot which is not allowing all the water to flow to the drain correctly, a licensed roofing contractor could either lower the portion of the roof covering close to the drain, or raise the portion where water is standing, either way will work, but I do recommend repairing this now, water lying at any location will cause that area of the roof covering to fail prematurely. See pictures 1-3. Pictures 4-6 shows the deterioration beginning on the asphalt based Roll Roofing Material which needs the entire flat portion resealed with a Reflective Roof Coating, including around the Air Conditioning Units.
|
| 4.1 | ROOF FLASHINGS, DRIP EDGE FLASHING Comments: Inspected | ||
There were no concern present with the metal roof flashings on
the building at the time of inspection. The two pictures are the metal
drip edge flashing and the membrane under the tiles, both in good
condition.
|
| 4.2 | ROOF PENETRATIONS, PLUMBING VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, CONDITION Comments: Repair or Replace | ||
I recommend all roof penetrations be resealed at the flat portions of
the roof system (far east, and west side of the building). They also
need to be checked annually, UV rays rapidly deteriorate the
asphalt base sealant.
|
| 4.3 | ROOF SHEATHING Comments: Inspected |
| Walking on the flat portion of the roof, the sheathing felt stable. Looking at the insulation attached to the underside of the roof sheathing from above the drop ceiling at the interior of the building I did not see any locations where rain water has entered the roof system. |
| 4.4 | ROOF DRAINAGE SYSTEMS Comments: Repair or Replace | |
| The roof drains need to be cleaned now, and every 6 months.
I removed as much debris as I could from the Drain Screen while I was on the roof, but the drain needs to be cleaned now, the area around the drain needs to be dry when the roof covering is sealed with the reflective roof coating (sealant).
|
| 4.5 | ROOF INSULATION Comments: Inspected | |||
| The insulation attached to the underside of the sheathing between
the trusses and rafters is Fiberglass Insulation with an R-Value of
38, there was no concern present.
I could see all the insulation from above ceiling tiles inside the building by removing the drop panels at numerous locations throughout the building.
|
Inspection Items
|
| 5.0 | MAIN WATER SHUTOFF DEVICE, LOCATION Comments: Inspected, Repair or Replace | ||
The water shutoff valve to turn off all water to the building is located
at the front. The valve is buried in stone and dirt which needs to be
removed so you can get to the valve if necessary.
|
| 5.1 | INTERIOR WATER SUPPLY MATERIAL, DISTRIBUTION SYSTEM, AND SUPPORTS Comments: Inspected |
| The interior water supply pipes are copper where the pipes are visible. They are supported correctly every where I could actually see them. |
| 5.2 | INTERIOR DRAIN, WASTE AND VENT PIPE MATERIAL, AND SUPPORTS Comments: Inspected |
| Interior drains and the drainage vent pipes are constructed of ABS, PVC plastic & steel piping, supported correctly where I can actually see them. |
| 5.3 | WATER HEATER(S) AND SYSTEM Comments: Inspected, Not Tested | ||
| The water heater is electric (15 gallon General Electric 2003),
located above the ceiling of the room in back of the Kitchenette
portion of the building.
I could not get right to the water heater because there are filing cabinets and boxes stacked against the wall directly under the water heater, but from what I could see there was no concern present. There is also a drip pan under the appliance in case a leak ever occurred in the future, with a drain line installed to the pan terminated to the exterior of the building on the north side.
|
| 5.4 | SEWER CLEANOUTS Comments: Inspected | |
The sanitary sewer cleanouts are accessible at the front of the
building.
|
Inspection Items
|
| 6.0 | MAIN ELECTRICAL METER AND DISTRIBUTION PANEL LOCATION Comments: Inspected | ||
Main electrical Service Meter and Switch Gear Equipment is located
at the rear of the building.
|
| 6.1 | MAIN ELECTRICAL PANEL AND DISTRIBUTION PANEL CONDITION Comments: Inspected |
| The electrical equipment was installed in a professional like manner. |
| 6.2 | MAIN ELECTRICAL SERVICE CONDUCTORS, TYPE, AMPERAGE AND VOLTAGE Comments: Inspected |
| The main Electrical Service Conductors providing power from the municipal supplier are Underground feeding the switchgear. The type of conductors from the Meter Panel to the Distribution Panels (sub-panels) are Copper 120/240 Volt, 200 Amp. three phase, and Copper 120/240 Volt at the 100 Amp. Sub-Panel. |
| 6.3 | ELECTRICAL SUB-PANELS LOCATION AND CONDITION Comments: Inspected | |||||
| There are two 200 Amp.
Sub-Panels in the mechanical room at the west side of the building, the
third panel which is a 100 Amp. Sub-Panel is in the closet of the
conference room at the front of the building, there was so many items
piled in front of it I could not get to the panel but there was no
concern with the other two. I will inspect the panel I could not access
when we do the reinspection of the repairs in the report after the
current tenant finishes moving. I took a picture of the sub-panel from the roof access which is in that closet, but I opened the hatch from the roof using my ladder, you cannot get to the roof access ladder in that closet until the current tenants move the rest of their personal belongings from the closet.
|
| 6.4 | MAIN OVERLOAD DEVICE AND THE ELECTRICAL SYSTEM GROUNDING Comments: Inspected | ||
The main overload devices to turn All electrical power off to the
entire building is Two 200 Amp. and One 100 Amp. Pull Type Fuse
Disconnects in the Main Service Panel at the rear exterior of the
building.
|
| 6.5 | BRANCH CIRCUIT WIRE TYPE AND CIRCUIT BREAKERS Comments: Inspected |
| Branch circuit conductors are Copper 120/240 Volt. The overload
devices the wires are connected to are Circuit Breakers at the Sub-Panels.
There was no concern with the conductor size connected to the various Circuit Breakers, they are compatible, which means the wire size is correct too what the Circuit Breaker is rated for. |
HEAT PUMPS: Electric Split System | FORCED AIR FURNACE(S): Split System Electric Heat Pump |
Inspection Items
|
| 7.0 | AIR CONDITIONING EQUIPMENT AND AIR HANDLER(S) Comments: Inspected, Repair or Replace | ||
| The air conditioning system for the building is Four Trane 2003
split system electric Heat Pumps located on the roof at the
northeast side of the building. The Air Handlers (blowers,
evaporator coils) are located above the ceiling in the building.
The Heat Pump pictured with arrows was sweating condensation water excessively at the outside coils, which is unusual (but it did operate correctly). I would ask the current owner when these Heat Pumps were serviced last. If they have not been serviced in the last 12 months all four need to be serviced now, but the Heat Pump in picture 1 needs service now. Testing the systems in the cooling mode the supply temperatures were 51-56 degrees (average) which is normal for this type of cooling system. All heating and cooling systems need to be serviced yearly by a qualified professional so they operate efficiently. Refrigerant levels need to be checked and the condenser coils cleaned. A system supplying air even one or two degrees lower after service will greatly reduce your electrical consumption.
|
| 7.1 | CONDENSATE DRAIN LINES, SYSTEM OVERFLOW PAN AT THE EQUIPMENT Comments: Inspected | |||
The Air Handlers do not have drip pans under them above the
ceilings in the building, these type are not required to have them,
but if I was buying the building I would have an HVAC contractor
install them in case the condensation drain lines ever became
plugged and condensation water started leaking from the Air
Handlers and onto the drop ceilings.
|
| 7.2 | REFRIGERANT LINES FOR AC EQUIPMENT Comments: Repair or Replace | |
The refrigerant pipe from the Air Conditioning Unit(s) to where they
enter the roof of the building need the insulation replaced for
maximum efficiency of the system.
|
| 7.3 | HEATING EQUIPMENT AND AIR HANDLER(S) Comments: Inspected |
| Trane Electric Heat Pumps are designed to heat or cool in different modes of the system. Operating the system it supplied temperatures in the low 100's (normal). Generally if a Heat Pump is operating properly in the heating mode the equipment will operate properly in the cooling mode, servicing the equipment yearly by a professional is highly recommended. |
| 7.4 | ELECTRICAL DISCONNECTS, WIRING, CONDUIT, FOR THE HEATING AND COOLING Comments: Inspected | |
The electrical disconnects for the Heat and Cooling equipment were
in normal condition on the roof next to the Heat Pumps.
|
| 7.5 | DISTRIBUTION DUCTS, REGISTERS, PIPING, SUPPORTS, FILTERS Comments: Inspected | ||
| Heat and Cooling distribution ducts and register vents were
inspected. Distribution ducts are insulated flexible and insulated
metal located in the ceilings.
The return Air Filters are located at the Air Handlers (above the ceilings, at four different locations) and have a filter change indicator device at the ceilings below each air handler, but I would ask the current owner when they were serviced last.
|
| 7.6 | THERMOSTAT(S) Comments: Inspected | |
Four Thermostats are properly fastened to the walls in the hallways
and operated as intended.
|
![]() | ![]() |
![]() | ![]() |
![]() | ![]() |
![]() | ![]() |
Inspection Items
|
| 8.0 | FLOORS Comments: Repair or Replace | ||
| There are various cracked floor tiles that need to be replaced at
the front entryway, it looks like they cracked because the
concrete floor under the tiles cracked, which is common for all
concrete floors, especially large ones if there was not sufficient
expansion joints in the concrete.
The tiles need to be replaced and a "Slip Sheet" installed under
the cracked tiles if there is a minor crack in the concrete floor to
prevent the tiles from cracking again. The easiest way to
describe a "Slip Sheet" is to say that this membrane isolates the
tile, bonding coat, and setting bed from the supporting element.
Slip Sheets are commonly asphalt impregnated papers, 15lb.
roofing felt, and polyethylene sheeting.
|
| 8.1 | WALLS, CEILINGS Comments: Repair or Replace | ||||||||||
| There are Numerous repairs needed on the sheetrock walls
throughout the building, (typical) normal settlement is common
and repairs to the walls are needed.
If the walls were cracked all the way to the floor from the ceiling and the foundation was also cracked, it would be a major concern, but I did not see anything unusual besides the fact it looked to me like none of the settlement cracks have been repaired since the building was constructed. There are a two moisture stains on the ceiling tiles, one in the conference room where the flat roof above it needs to be sealed and water is lying near the roof drain, which could be directly related to the stains, but nothing was leaking today. The roof needs to be repaired above this portion of the building (see roof section of this report).
|
| 8.2 | WALL CABINETS Comments: Inspected |
| There was no concern present with any of the cabinets in the building, they are correctly installed, and attached to the walls correctly. |
| 8.3 | INTERIOR DOORS Comments: Inspected |
| Interior doors were inspected. They operated and latched properly at the time of this inspection. |
| 8.4 | CEILING FANS Comments: Inspected |
| Ceiling fans functioned properly when tested today. |
| 8.5 | ELECTRICAL WIRING, OUTLETS, SWITCHES, AND LIGHTING Comments: Inspected |
| I tested the accessible electrical receptacles and switches, no concern was present, they are wired correctly. |
| 8.6 | SPRINKLER SYSTEM Comments: Not Tested | |||
| The system was inspected in May of 2007, I would have the
company noted in the inspection certificate (pictured) reinspect the
system when you close escrow.
Abrigo Fire Protection
|
| 8.7 | EXIT SIGN AND EMERGENCY LIGHTING Comments: Inspected | |
The exit signs were illuminated, the emergency lighting was
manually tested, the lights came on during the test.
|
Inspection Items
|
| 9.0 | WALK-IN SHOWER(S) Comments: Inspected | |
The condition was acceptable and the fixture operated correctly.
|
| 9.1 | SINKS, COUNTERTOPS, CABINETS Comments: Inspected | |
The sinks and faucets in restrooms operated correctly today.
|
| 9.2 | TOILETS Comments: Inspected | ||
The toilets are correctly installed, no visible leaks present and
flushed properly.
|
| 9.3 | URINALS Comments: Inspected | |
There was no concern present, the fixture flushed correctly, the
sloan valve did not have any active leaks.
|
| 9.4 | TOWEL HOLDERS & HAND DRYERS Comments: Inspected |
| The paper towel holders are attached to the walls correctly. |
| 9.5 | DRAINAGE PIPES Comments: Inspected |
| There were no active leaks at the time of this inspection. |
| 9.6 | WATER VALVES AND SUPPLY LINES Comments: Inspected |
| There were no active leaks at the time of this inspection. |
| 9.7 | WATER PRESSURE, AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected |
| The water pressure in the restrooms was normal. The drains emptied correctly. |
| 9.8 | ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Ground fault circuit interrupters were tested in restrooms, no concerns were present. The lighting functioned properly. |
| 9.9 | CEILING EXHAUST VENTILATION Comments: Inspected |
| Restroom ceiling ventilation fans were functional and the vent pipes are terminated above the roof of the building. |
Inspection Items
|
| 10.0 | KITCHEN CABINETS AND COUNTERTOPS Comments: Inspected |
| Cabinets and countertops are in normal condition. |
| 10.1 | KITCHEN SINK AND FAUCET Comments: Inspected |
| The faucet operated correctly. The sink was in normal condition. |
| 10.2 | SINK DRAINAGE PIPES Comments: Inspected | ||
There were no active leaks at the time of this inspection.
|
| 10.3 | SINK WATER VALVE AND SUPPLY PIPING Comments: Inspected |
| There were no leaks at the time of this inspection. |
| 10.4 | WATER PRESSURE AND DRAINAGE FUNCTIONAL FLOW Comments: Inspected |
| The water pressure was acceptable and drains emptied correctly. |
| 10.5 | KITCHEN ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING Comments: Inspected |
| Ground fault circuit interrupters were tested. Lighting functioned correctly. |
| 10.6 | FOOD DISPOSER Comments: Inspected |
| Disposer functioned properly. Electrical and plumbing connections were consistent with current standards. |
| 10.7 | DISHWASHER Comments: Inspected |
| I operated manually through a rinse cycle (functioned properly). Plumbing and electrical connections are consistent with current standards. |
| 10.8 | TRASH COMPACTOR Comments: Inspected |
| The trash compactor was empty, but it did turn on and off correctly. |
| 10.9 | REFRIGERATOR Comments: Inspected |
| The refrigerator-freezer was operating today. |
![]() Inspect Arizona Companies, Inc.
10599 E. Betony Dr. |
|
Customer |
|
Property Address |
|
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the building.
This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
| 1. GENERAL BUILDING AND SITE INFORMATION | ||||||||||||||||||
|
| 3. EXTERIOR OF BUILDING, MATERIALS USED AND CONDITION | ||||||||||||||||||
|
| 4. ROOF MATERIAL TYPE AND CONDITION | ||||||||||||||||||
|
| 5. PLUMBING SYSTEMS OF THE BUILDING | ||||||
|
| 7. AIR CONDITIONING AND HEATING EQUIPMENT | ||||||||||||
|
| 8. INTERIOR OF THE ENTIRE BUILDING | ||||||||||||||||||
|
There is negative drainage at these areas next to the foundation of the building, and the final grade (landscape rock) is too close to the bottom of the exterior finished wall and should be lowered as much as possible while still allowing the grade to slope so rain water drains away from the foundation.
The roof drains, (four sets of drain pipes total) (of the two) I have pictured (one pipe is a primary drain, the other is the secondary) need to be extended so they do not terminate next to the concrete foundation.
A contractor can add pipe and fittings to make this needed upgrade.