Inspection Report

Prepared For:
Patrick Wagner

Property Address:
2150 W. Southern Ave.
Phoenix, AZ. 85008

Inspect Arizona Companies, Inc.

Dale Duffy: AZ# 43396
10599 E. Betony Dr.
Scottsdale, AZ. 85255
602.402.5305
Top Table of Contents Bottom
 

Table of Contents


Top Table of Contents Bottom
 
Date: 2/18/2006 Time: 08:55 AM Report ID: 2.18.06
Property:
2150 W. Southern Ave.
Phoenix, AZ. 85008
Customer:
Patrick Wagner
Real Estate Professional:
Commercial Property Realtors

The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor or professional.

Inspected: This term means I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing normal wear and tear. The notation does not mean that the item is perfect but does meet a reasonable standard on the day of inspection.

Repair or Replace: The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Requires Immediate Attention: The item, component or unit needs immediate attention by a qualified professional or contractor for the safety or health of the occupants of the building. Could cause further major deterioration, or complete failure of a system or component. Worsen appreciably, cause damage, or be a serious hazard.

Unsafe: A condition in a readily accessible, installed system or component which is judged to be a significant risk of personal injury during normal day to day use. The risk may be due to damage, deterioration, improper installation or a change in adopted construction standards.

Not Tested: I did inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not testing or operating.

IMPORTANT NOTICE TO THIRD PARTIES:  Receipt of this report by anyone other than the above listed party(s) is not authorized by Inspect Arizona Companies, Inc. This report is prepared for the sole and exclusive use for the client who signed the INSPECTION AGREEMENT and is subject to the terms and conditions agreed upon.  This Inspection Report is a product, and is copyrighted by Inspect Arizona Companies, Inc. at the date of this inspection.  Duplication by any means whatsoever is prohibited without prior written permission and authorization from Inspect Arizona Companies, Inc.  Unauthorized duplication, use, or reliance of this report shall constitute all parties agreed upon to hold harmless, whether individual, joint or otherwise, Dale Duffy and Inspect Arizona Companies, Inc., their successor's and assignee's.

PERMITS/BUILDING CODE VIOLATIONS:  If you are concerned about code violations or building permit information you should: 1) Contract with our company to research permit information available at the appropriate building and safety office, 2) If you have additional concerns with regard to code violations you may contract for a code compliance survey of the property. 

You have contracted with us to perform a commercial inspection in accordance with Arizona industry standards for the inspection profession. This is different from our technically exhaustive inspection which takes several days to complete, involves the use of specialized instruments, the dismantling of equipment, video scanning, destructive testing and laboratory analysis of possible contaminates. Our purpose is to identify defects or adverse conditions that need additional evaluation, are safety concerns or may lead to costs that would significantly affect your evaluation of the property at the time of this inspection.

Client Is Present:
Yes

Building Faces:
East

Weather:
Clear

Temperature:
Over 65 degrees

Rain in last 3 days:
Yes

 
Top Table of Contents Bottom
1.  GENERAL BUILDING AND SITE INFORMATION
The conditions reported in this inspection report are for the sole purpose of identifying conditions which exist at the time of this Inspection. We cannot, and do not, imply or guess, how long any item in this inspection report will serve the purpose it was designed or manufactured for. Warranty insurance is for the unforeseen future failure of a buildings fixtures, systems and components. Furthermore, any reported items needing repair, service, or replacement should be done before the close of escrow by qualified professionals.

 

Inspection Items
1.0 BASIC REPORT INFORMATION OR BUILDING CHARACTERISTICS
Comments: Inspected
The current tenants were in the process of moving out today. I inspected all locations I could access where personal belongings were not piled.

The most expensive repair in my opinion will be to repair all the settlement and shrinkage cracks in the sheetrock walls at the interior of the building. The roof repairs at the flat portion in my opinion as a past commercial builder should range from
1.1 GENERAL EXTERIOR SITE DRAINAGE
Comments: Repair or Replace
When the building was constructed the grade of the lot and walkways at the south, east and west side of the building should have been lower than they currently are (as built).

There is negative drainage at these areas next to the foundation of the building, and the final grade (landscape rock) is too close to the bottom of the exterior finished wall and should be lowered as much as possible while still allowing the grade to slope so rain water drains away from the foundation.

The roof drains, (four sets of drain pipes total) (of the two) I have pictured (one pipe is a primary drain, the other is the secondary) need to be extended so they do not terminate next to the concrete foundation.

A contractor can add pipe and fittings to make this needed upgrade.

1.1 Picture 1
1.1 Picture 2
1.1 Picture 3
1.1 Picture 4
1.2 TREE OR VEGETATION NEXT TO THE BUILDING
Comments: Repair or Replace
I recommend trimming any tree branches in direct contact with the building. The wind moving the branches will cause damage to building components (roof , fascia, stucco).
1.3 DRIVEWAY, PARKING LOT, WALKWAYS, PATIOS, ENTRYWAYS, CONDITION
Comments: Inspected
The exterior hard surfaces were in normal condition at the time of this inspection. Minor cracks in concrete are normal, considered typical.
1.4 IRRIGATION PIPING
Comments: Repair or Replace
I do not know if the building association is responsible for the irrigation system or you are, but there are numerous heads missing from the drip irrigation 1/4 inch lines to the different plants and bushes.

Regardless of who is responsible for the system I recommend a licensed landscape professional look at all the irrigation lines to the vegetation and make the necessary repairs needed.

1.4 Picture 1
1.4 Picture 2
The items in the report which need further evaluation or repair should be done by licensed contractors. I also recommend getting three bids on any item and check the contractors current standing with the Arizona Registrar of Contractors. The contractors license, insurance, and possible past complaints are available at http://www.rc.state.az.us
Top Table of Contents Bottom
2.  STRUCTURAL LOAD BEARING COMPONENTS AND BUILDING MATERIALS USED

 

Inspection Items
2.0 FOUNDATION TYPE; CONDITION
Comments: Inspected, Not Tested
The foundation of this building is poured concrete, no major concerns were visible at the time of inspection (where I could actually see it, landscape rock is to high).

Minor cracks are common in concrete products and the condition of this foundation is considered typical where I can actually see the concrete.

2.1 FLOOR TYPE; CONDITION
Comments: Inspected
Floors in the building are constructed of poured concrete. The conditions are acceptable with regard to the structural integrity of the concrete slab on grade floor system.

There are floor coverings present except in the back room of the building where I can see expansion joints, which is probably why the tiles are cracked at the front of the building, concrete expands and contracts, which causes the tiles to crack, if there was differential movement up and down it would be a issue, but I did not see any.

There was no visual evidence of Major Wall Cracks at the Floor Level which would tell me a concern is present.

2.2 EXTERIOR AND INTERIOR LOAD BEARING WALLS; TYPE; CONDITION
Comments: Inspected
The exterior and interior walls are constructed with wood and steel framing materials, the walls are covered with sheetrock at the interior. There was no visible concern with the wall framing structurally.
2.3 CEILING MATERIAL; TYPE; CONDITION
Comments: Inspected
Ceilings in the building were constructed with a Drop Panel System. The condition was acceptable, no concerns were present today.
2.4 ROOF STRUCTURE TYPE; CONDITION
Comments: Inspected
The roof structure of this building is constructed with engineered wood trusses & rafters with oriented strand board (OSB) attached to the trusses for roof sheathing. Visually inspecting the condition of the components above the ceilings there was no concern where access could be gained.
2.5 POSTS, BEAMS, COLUMNS TYPE; CONDITION
Comments: Inspected
The load bearing beams I could see above the ceiling tiles are in normal condition, at the front of the building there is also large wood beams, no concern was present there either.
Top Table of Contents Bottom
3.  EXTERIOR OF BUILDING, MATERIALS USED AND CONDITION
It is important to maintain a property, including exterior wall surfaces, wood trim, and other hard surfaces. It is particularly important to keep walls sealed, which provide the only barrier against deterioration, unsealed cracks around windows, doors, and thresholds can allow moisture intrusion, which is the principle cause of the deterioration of any surface.

 

Inspection Items
3.0 EXTERIOR WALLS, CONDITION
Comments: Repair or Replace
The building has an exterior insulated finish system, commonly know as stucco. Buildings in Arizona experience extreme heat in the summer and sometimes rather cold conditions in the winter, which cause the building materials to expand and contract.

Stucco will exhibit cracks in the finish from these conditions which cannot be stopped. When cracks become wide enough for rain water to enter in back of the finish, caulk should be applied to the cracks and touched up with paint. Cracks in stucco are not considered unusual, and are found on all buildings.

I recommend a licensed contractor go around the building and caulk all the cracks with a good quality paintable caulk and touch up the repairs with new paint before you close escrow.

3.0 Picture 1
3.0 Picture 2
3.0 Picture 3
3.1 STUCCO WEEP SCREED FLASHING
Comments: Inspected
The weep flashing at the bottom of the exterior stucco walls is installed correctly.
3.2 BRICK, ROCK, VENEER
Comments: Inspected
The rock veneer is in normal condition.
3.3 SOFFITS, FASCIA, EAVES, TRIM
Comments: Inspected
The exterior trim, fascia, and eaves on this building are in normal condition.
3.4 EXTERIOR WINDOWS AND FLASHINGS, INTERIOR CONDITIONS NOTED
Comments: Inspected
Windows are commercial grade glass. The conditions were good at the time of this inspection.
3.5 WINDOW FRAMES
Comments: Repair or Replace
The window frames should be caulked at the exterior where they meet the stucco, some cracks are excessive from shrinkage and settlement but need repair.
3.6 EXTERIOR DOORS AND WEATHER STRIPPING
Comments: Inspected
The exterior entrance doors operated and latched correctly when inspected. The weather stripping was functional.
3.7 EXTERIOR ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING
Comments: Inspected
Exterior outlets are Ground fault circuit interrupters, there was no concern present. The exterior lights functioned correctly also.
3.8 EXTERIOR PLUMBING, FAUCETS
Comments: Repair or Replace
The hose faucets functioned correctly, but the stucco needs to be caulked around the one at the rear of the building.
3.8 Picture 1
Top Table of Contents Bottom
4.  ROOF MATERIAL TYPE AND CONDITION
Every roof will wear differently relative to its age, the quality of the material, the method of the installation, the exposure to direct sun light or other prevalent weather conditions, and the regularity of the maintenance. Regardless of its design life, every roof is only as good as the waterproof membrane beneath it, which is concealed and cannot be examined without removing the roof material.

 

Inspection Items
4.0 ROOF COVERINGS, TYPE, CONDITION
Comments: Repair or Replace
The roof system was inspected by walking the flat portions and I used a ladder to inspect the clay tile areas, there was no concern with the clay tiles, but the east side (front) of the building needs the flat roof portion sealed with a Reflective Roof Coating.

This portion of the roof is also holding rain water at the northeast portion by the roof drain. When the roof was built, there is a low spot which is not allowing all the water to flow to the drain correctly, a licensed roofing contractor could either lower the portion of the roof covering close to the drain, or raise the portion where water is standing, either way will work, but I do recommend repairing this now, water lying at any location will cause that area of the roof covering to fail prematurely.

See pictures 1-3.

Pictures 4-6 shows the deterioration beginning on the asphalt based Roll Roofing Material which needs the entire flat portion resealed with a Reflective Roof Coating, including around the Air Conditioning Units.

4.0 Picture 1
4.0 Picture 2
4.0 Picture 3
4.0 Picture 4
4.0 Picture 5
4.0 Picture 6
4.0 Picture 7
4.0 Picture 8
4.0 Picture 9
4.1 ROOF FLASHINGS, DRIP EDGE FLASHING
Comments: Inspected
There were no concern present with the metal roof flashings on the building at the time of inspection. The two pictures are the metal drip edge flashing and the membrane under the tiles, both in good condition.
4.1 Picture 1
4.1 Picture 2
4.2 ROOF PENETRATIONS, PLUMBING VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, CONDITION
Comments: Repair or Replace
I recommend all roof penetrations be resealed at the flat portions of the roof system (far east, and west side of the building). They also need to be checked annually, UV rays rapidly deteriorate the asphalt base sealant.
4.2 Picture 1
4.2 Picture 2
4.3 ROOF SHEATHING
Comments: Inspected
Walking on the flat portion of the roof, the sheathing felt stable.

Looking at the insulation attached to the underside of the roof sheathing from above the drop ceiling at the interior of the building I did not see any locations where rain water has entered the roof system.
4.4 ROOF DRAINAGE SYSTEMS
Comments: Repair or Replace
The roof drains need to be cleaned now, and every 6 months.

I removed as much debris as I could from the Drain Screen while I was on the roof, but the drain needs to be cleaned now, the area around the drain needs to be dry when the roof covering is sealed with the reflective roof coating (sealant).

4.4 Picture 1
4.5 ROOF INSULATION
Comments: Inspected
The insulation attached to the underside of the sheathing between the trusses and rafters is Fiberglass Insulation with an R-Value of 38, there was no concern present.

I could see all the insulation from above ceiling tiles inside the building by removing the drop panels at numerous locations throughout the building.

4.5 Picture 1
4.5 Picture 2
4.5 Picture 3
Top Table of Contents Bottom
5.  PLUMBING SYSTEMS OF THE BUILDING

 

Inspection Items
5.0 MAIN WATER SHUTOFF DEVICE, LOCATION
Comments: Inspected, Repair or Replace
The water shutoff valve to turn off all water to the building is located at the front. The valve is buried in stone and dirt which needs to be removed so you can get to the valve if necessary.
5.0 Picture 1
5.0 Picture 2
5.1 INTERIOR WATER SUPPLY MATERIAL, DISTRIBUTION SYSTEM, AND SUPPORTS
Comments: Inspected
The interior water supply pipes are copper where the pipes are visible. They are supported correctly every where I could actually see them.
5.2 INTERIOR DRAIN, WASTE AND VENT PIPE MATERIAL, AND SUPPORTS
Comments: Inspected
Interior drains and the drainage vent pipes are constructed of ABS, PVC plastic & steel piping, supported correctly where I can actually see them.
5.3 WATER HEATER(S) AND SYSTEM
Comments: Inspected, Not Tested
The water heater is electric (15 gallon General Electric 2003), located above the ceiling of the room in back of the Kitchenette portion of the building.

I could not get right to the water heater because there are filing cabinets and boxes stacked against the wall directly under the water heater, but from what I could see there was no concern present. There is also a drip pan under the appliance in case a leak ever occurred in the future, with a drain line installed to the pan terminated to the exterior of the building on the north side.

5.3 Picture 1
5.3 Picture 2
5.4 SEWER CLEANOUTS
Comments: Inspected
The sanitary sewer cleanouts are accessible at the front of the building.
5.4 Picture 1
Top Table of Contents Bottom
6.  ELECTRICAL SYSTEM

 

Inspection Items
6.0 MAIN ELECTRICAL METER AND DISTRIBUTION PANEL LOCATION
Comments: Inspected
Main electrical Service Meter and Switch Gear Equipment is located at the rear of the building.
6.0 Picture 1
6.0 Picture 2
6.1 MAIN ELECTRICAL PANEL AND DISTRIBUTION PANEL CONDITION
Comments: Inspected
The electrical equipment was installed in a professional like manner.
6.2 MAIN ELECTRICAL SERVICE CONDUCTORS, TYPE, AMPERAGE AND VOLTAGE
Comments: Inspected
The main Electrical Service Conductors providing power from the municipal supplier are Underground feeding the switchgear. The type of conductors from the Meter Panel to the Distribution Panels (sub-panels) are Copper 120/240 Volt, 200 Amp. three phase, and Copper 120/240 Volt at the 100 Amp. Sub-Panel.
6.3 ELECTRICAL SUB-PANELS LOCATION AND CONDITION
Comments: Inspected
There are two 200 Amp. Sub-Panels in the mechanical room at the west side of the building, the third panel which is a 100 Amp. Sub-Panel is in the closet of the conference room at the front of the building, there was so many items piled in front of it I could not get to the panel but there was no concern with the other two. I will inspect the panel I could not access when we do the reinspection of the repairs in the report after the current tenant finishes moving.

I took a picture of the sub-panel from the roof access which is in that closet, but I opened the hatch from the roof using my ladder, you cannot get to the roof access ladder in that closet until the current tenants move the rest of their personal belongings from the closet.

6.3 Picture 1
6.3 Picture 2
6.3 Picture 3
6.3 Picture 4
6.3 Picture 5
6.4 MAIN OVERLOAD DEVICE AND THE ELECTRICAL SYSTEM GROUNDING
Comments: Inspected
The main overload devices to turn All electrical power off to the entire building is Two 200 Amp. and One 100 Amp. Pull Type Fuse Disconnects in the Main Service Panel at the rear exterior of the building.
6.4 Picture 1
6.4 Picture 2
6.5 BRANCH CIRCUIT WIRE TYPE AND CIRCUIT BREAKERS
Comments: Inspected
Branch circuit conductors are Copper 120/240 Volt. The overload devices the wires are connected to are Circuit Breakers at the Sub-Panels.

There was no concern with the conductor size connected to the various Circuit Breakers, they are compatible, which means the wire size is correct too what the Circuit Breaker is rated for.

Top Table of Contents Bottom
7.  AIR CONDITIONING AND HEATING EQUIPMENT
The heating and cooling systems should be inspected and serviced on an annual basis.

I recommend obtaining from the seller well before close of escrow any documents concerning regular maintenance and service. If it cannot be proven that the heating and cooling systems have been inspected and serviced within the past twelve months by a Licensed HVAC specialist, I recommend the system be serviced now.

Styles & Materials
HEAT PUMPS:
Electric Split System
FORCED AIR FURNACE(S):
Split System Electric Heat Pump
 
Inspection Items
7.0 AIR CONDITIONING EQUIPMENT AND AIR HANDLER(S)
Comments: Inspected, Repair or Replace
The air conditioning system for the building is Four Trane 2003 split system electric Heat Pumps located on the roof at the northeast side of the building. The Air Handlers (blowers, evaporator coils) are located above the ceiling in the building.

The Heat Pump pictured with arrows was sweating condensation water excessively at the outside coils, which is unusual (but it did operate correctly). I would ask the current owner when these Heat Pumps were serviced last. If they have not been serviced in the last 12 months all four need to be serviced now, but the Heat Pump in picture 1 needs service now.

Testing the systems in the cooling mode the supply temperatures were 51-56 degrees (average) which is normal for this type of cooling system. All heating and cooling systems need to be serviced yearly by a qualified professional so they operate efficiently. Refrigerant levels need to be checked and the condenser coils cleaned. A system supplying air even one or two degrees lower after service will greatly reduce your electrical consumption.

7.0 Picture 1
7.0 Picture 2
7.1 CONDENSATE DRAIN LINES, SYSTEM OVERFLOW PAN AT THE EQUIPMENT
Comments: Inspected
The Air Handlers do not have drip pans under them above the ceilings in the building, these type are not required to have them, but if I was buying the building I would have an HVAC contractor install them in case the condensation drain lines ever became plugged and condensation water started leaking from the Air Handlers and onto the drop ceilings.
7.1 Picture 1
7.1 Picture 2
7.1 Picture 3
7.2 REFRIGERANT LINES FOR AC EQUIPMENT
Comments: Repair or Replace
The refrigerant pipe from the Air Conditioning Unit(s) to where they enter the roof of the building need the insulation replaced for maximum efficiency of the system.
7.2 Picture 1
7.3 HEATING EQUIPMENT AND AIR HANDLER(S)
Comments: Inspected
Trane Electric Heat Pumps are designed to heat or cool in different modes of the system. Operating the system it supplied temperatures in the low 100's (normal). Generally if a Heat Pump is operating properly in the heating mode the equipment will operate properly in the cooling mode, servicing the equipment yearly by a professional is highly recommended.
7.4 ELECTRICAL DISCONNECTS, WIRING, CONDUIT, FOR THE HEATING AND COOLING
Comments: Inspected
The electrical disconnects for the Heat and Cooling equipment were in normal condition on the roof next to the Heat Pumps.
7.4 Picture 1
7.5 DISTRIBUTION DUCTS, REGISTERS, PIPING, SUPPORTS, FILTERS
Comments: Inspected
Heat and Cooling distribution ducts and register vents were inspected. Distribution ducts are insulated flexible and insulated metal located in the ceilings.

The return Air Filters are located at the Air Handlers (above the ceilings, at four different locations) and have a filter change indicator device at the ceilings below each air handler, but I would ask the current owner when they were serviced last.

7.5 Picture 1
7.5 Picture 2
7.6 THERMOSTAT(S)
Comments: Inspected
Four Thermostats are properly fastened to the walls in the hallways and operated as intended.
7.6 Picture 1
The components of the air conditioning and heating systems have a design life ranging from ten to twenty years, but can prematurely fail because of poor maintenance. We test and evaluate them in accordance with the Arizona standards of practice, which means we do not dismantle and inspect the concealed portions of the heat exchanger, evaporator or condensing coils. We perform a conscientious evaluation of both systems, but we are not specialists. Therefore, in accordance with what is written in this report, it is essential that any recommendations for service or a second opinion by a heating and cooling specialist be done before the close of escrow, because a specialist could reveal additional defects after dismantling the equipment for service, which could affect your evaluation of the property. Heating and cooling equipment are generally only guaranteed by the manufacturer for one year after installation.
Top Table of Contents Bottom
8.  INTERIOR OF THE ENTIRE BUILDING

 

Inspection Items
8.0 FLOORS
Comments: Repair or Replace
There are various cracked floor tiles that need to be replaced at the front entryway, it looks like they cracked because the concrete floor under the tiles cracked, which is common for all concrete floors, especially large ones if there was not sufficient expansion joints in the concrete.

The tiles need to be replaced and a "Slip Sheet" installed under the cracked tiles if there is a minor crack in the concrete floor to prevent the tiles from cracking again. The easiest way to describe a "Slip Sheet" is to say that this membrane isolates the tile, bonding coat, and setting bed from the supporting element. Slip Sheets are commonly asphalt impregnated papers, 15lb. roofing felt, and polyethylene sheeting.

The concrete under the tiles expands and contracts from heat, and cooling which is the primary cause of tiles cracking installed on concrete floors, a Slip Sheet installed under the cracked tiles before they are replaced will prevent them from cracking in the future.

8.0 Picture 1
8.0 Picture 2
8.1 WALLS, CEILINGS
Comments: Repair or Replace
There are Numerous repairs needed on the sheetrock walls throughout the building, (typical) normal settlement is common and repairs to the walls are needed.

If the walls were cracked all the way to the floor from the ceiling and the foundation was also cracked, it would be a major concern, but I did not see anything unusual besides the fact it looked to me like none of the settlement cracks have been repaired since the building was constructed.

There are a two moisture stains on the ceiling tiles, one in the conference room where the flat roof above it needs to be sealed and water is lying near the roof drain, which could be directly related to the stains, but nothing was leaking today. The roof needs to be repaired above this portion of the building (see roof section of this report).

8.1 Picture 1
8.1 Picture 2
8.1 Picture 3
8.1 Picture 4
8.1 Picture 5
8.1 Picture 6
8.1 Picture 7
8.1 Picture 8
8.1 Picture 9
8.1 Picture 10
8.2 WALL CABINETS
Comments: Inspected
There was no concern present with any of the cabinets in the building, they are correctly installed, and attached to the walls correctly.
8.3 INTERIOR DOORS
Comments: Inspected
Interior doors were inspected. They operated and latched properly at the time of this inspection.
8.4 CEILING FANS
Comments: Inspected
Ceiling fans functioned properly when tested today.
8.5 ELECTRICAL WIRING, OUTLETS, SWITCHES, AND LIGHTING
Comments: Inspected
I tested the accessible electrical receptacles and switches, no concern was present, they are wired correctly.
8.6 SPRINKLER SYSTEM
Comments: Not Tested
The system was inspected in May of 2007, I would have the company noted in the inspection certificate (pictured) reinspect the system when you close escrow.

Abrigo Fire Protection
602.237.2588

8.6 Picture 1
8.6 Picture 2
8.6 Picture 3
8.7 EXIT SIGN AND EMERGENCY LIGHTING
Comments: Inspected
The exit signs were illuminated, the emergency lighting was manually tested, the lights came on during the test.
8.7 Picture 1
Top Table of Contents Bottom
9.  BATHROOMS

 

Inspection Items
9.0 WALK-IN SHOWER(S)
Comments: Inspected
The condition was acceptable and the fixture operated correctly.
9.0 Picture 1
9.1 SINKS, COUNTERTOPS, CABINETS
Comments: Inspected
The sinks and faucets in restrooms operated correctly today.
9.1 Picture 1
9.2 TOILETS
Comments: Inspected
The toilets are correctly installed, no visible leaks present and flushed properly.
9.2 Picture 1
9.2 Picture 2
9.3 URINALS
Comments: Inspected
There was no concern present, the fixture flushed correctly, the sloan valve did not have any active leaks.
9.3 Picture 1
9.4 TOWEL HOLDERS & HAND DRYERS
Comments: Inspected
The paper towel holders are attached to the walls correctly.
9.5 DRAINAGE PIPES
Comments: Inspected
There were no active leaks at the time of this inspection.
9.6 WATER VALVES AND SUPPLY LINES
Comments: Inspected
There were no active leaks at the time of this inspection.
9.7 WATER PRESSURE, AND DRAINAGE FUNCTIONAL FLOW
Comments: Inspected
The water pressure in the restrooms was normal. The drains emptied correctly.
9.8 ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING
Comments: Inspected
Ground fault circuit interrupters were tested in restrooms, no concerns were present. The lighting functioned properly.
9.9 CEILING EXHAUST VENTILATION
Comments: Inspected
Restroom ceiling ventilation fans were functional and the vent pipes are terminated above the roof of the building.
Top Table of Contents Bottom
10.  KITCHEN, CABINETS, COUNTERS, APPLIANCES

 

Inspection Items
10.0 KITCHEN CABINETS AND COUNTERTOPS
Comments: Inspected
Cabinets and countertops are in normal condition.
10.1 KITCHEN SINK AND FAUCET
Comments: Inspected
The faucet operated correctly. The sink was in normal condition.
10.2 SINK DRAINAGE PIPES
Comments: Inspected
There were no active leaks at the time of this inspection.
10.2 Picture 1
10.2 Picture 2
10.3 SINK WATER VALVE AND SUPPLY PIPING
Comments: Inspected
There were no leaks at the time of this inspection.
10.4 WATER PRESSURE AND DRAINAGE FUNCTIONAL FLOW
Comments: Inspected
The water pressure was acceptable and drains emptied correctly.
10.5 KITCHEN ELECTRICAL OUTLETS, GROUND FAULT CIRCUITS, LIGHTING
Comments: Inspected
Ground fault circuit interrupters were tested. Lighting functioned correctly.
10.6 FOOD DISPOSER
Comments: Inspected
Disposer functioned properly. Electrical and plumbing connections were consistent with current standards.
10.7 DISHWASHER
Comments: Inspected
I operated manually through a rinse cycle (functioned properly). Plumbing and electrical connections are consistent with current standards.
10.8 TRASH COMPACTOR
Comments: Inspected
The trash compactor was empty, but it did turn on and off correctly.
10.9 REFRIGERATOR
Comments: Inspected
The refrigerator-freezer was operating today.

Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2007 : Licensed To Inspect Arizona Companies, Inc.
Top Table of Contents Bottom
 

SUMMARY


Inspect Arizona Companies, Inc.

10599 E. Betony Dr.
Scottsdale, AZ. 85255
602.402.5305

Customer
Patrick Wagner

Property Address
2150 W. Southern Ave.
Phoenix, AZ. 85008

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation.

This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the building.

This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  GENERAL BUILDING AND SITE INFORMATION
1.1   GENERAL EXTERIOR SITE DRAINAGE
  Repair or Replace
When the building was constructed the grade of the lot and walkways at the south, east and west side of the building should have been lower than they currently are (as built).

There is negative drainage at these areas next to the foundation of the building, and the final grade (landscape rock) is too close to the bottom of the exterior finished wall and should be lowered as much as possible while still allowing the grade to slope so rain water drains away from the foundation.

The roof drains, (four sets of drain pipes total) (of the two) I have pictured (one pipe is a primary drain, the other is the secondary) need to be extended so they do not terminate next to the concrete foundation.

A contractor can add pipe and fittings to make this needed upgrade.

1.2   TREE OR VEGETATION NEXT TO THE BUILDING
  Repair or Replace
I recommend trimming any tree branches in direct contact with the building. The wind moving the branches will cause damage to building components (roof , fascia, stucco).
1.4   IRRIGATION PIPING
  Repair or Replace
I do not know if the building association is responsible for the irrigation system or you are, but there are numerous heads missing from the drip irrigation 1/4 inch lines to the different plants and bushes.

Regardless of who is responsible for the system I recommend a licensed landscape professional look at all the irrigation lines to the vegetation and make the necessary repairs needed.


3.  EXTERIOR OF BUILDING, MATERIALS USED AND CONDITION
3.0   EXTERIOR WALLS, CONDITION
  Repair or Replace
The building has an exterior insulated finish system, commonly know as stucco. Buildings in Arizona experience extreme heat in the summer and sometimes rather cold conditions in the winter, which cause the building materials to expand and contract.

Stucco will exhibit cracks in the finish from these conditions which cannot be stopped. When cracks become wide enough for rain water to enter in back of the finish, caulk should be applied to the cracks and touched up with paint. Cracks in stucco are not considered unusual, and are found on all buildings.

I recommend a licensed contractor go around the building and caulk all the cracks with a good quality paintable caulk and touch up the repairs with new paint before you close escrow.

3.5   WINDOW FRAMES
  Repair or Replace
The window frames should be caulked at the exterior where they meet the stucco, some cracks are excessive from shrinkage and settlement but need repair.
3.8   EXTERIOR PLUMBING, FAUCETS
  Repair or Replace
The hose faucets functioned correctly, but the stucco needs to be caulked around the one at the rear of the building.

4.  ROOF MATERIAL TYPE AND CONDITION
4.0   ROOF COVERINGS, TYPE, CONDITION
  Repair or Replace
The roof system was inspected by walking the flat portions and I used a ladder to inspect the clay tile areas, there was no concern with the clay tiles, but the east side (front) of the building needs the flat roof portion sealed with a Reflective Roof Coating.

This portion of the roof is also holding rain water at the northeast portion by the roof drain. When the roof was built, there is a low spot which is not allowing all the water to flow to the drain correctly, a licensed roofing contractor could either lower the portion of the roof covering close to the drain, or raise the portion where water is standing, either way will work, but I do recommend repairing this now, water lying at any location will cause that area of the roof covering to fail prematurely.

See pictures 1-3.

Pictures 4-6 shows the deterioration beginning on the asphalt based Roll Roofing Material which needs the entire flat portion resealed with a Reflective Roof Coating, including around the Air Conditioning Units.

4.2   ROOF PENETRATIONS, PLUMBING VENTS, ATTIC VENTS, SKYLIGHTS, CHIMNEYS, CONDITION
  Repair or Replace
I recommend all roof penetrations be resealed at the flat portions of the roof system (far east, and west side of the building). They also need to be checked annually, UV rays rapidly deteriorate the asphalt base sealant.
4.4   ROOF DRAINAGE SYSTEMS
  Repair or Replace
The roof drains need to be cleaned now, and every 6 months.

I removed as much debris as I could from the Drain Screen while I was on the roof, but the drain needs to be cleaned now, the area around the drain needs to be dry when the roof covering is sealed with the reflective roof coating (sealant).


5.  PLUMBING SYSTEMS OF THE BUILDING
5.0   MAIN WATER SHUTOFF DEVICE, LOCATION
  Inspected, Repair or Replace
The water shutoff valve to turn off all water to the building is located at the front. The valve is buried in stone and dirt which needs to be removed so you can get to the valve if necessary.

7.  AIR CONDITIONING AND HEATING EQUIPMENT
7.0   AIR CONDITIONING EQUIPMENT AND AIR HANDLER(S)
  Inspected, Repair or Replace
The air conditioning system for the building is Four Trane 2003 split system electric Heat Pumps located on the roof at the northeast side of the building. The Air Handlers (blowers, evaporator coils) are located above the ceiling in the building.

The Heat Pump pictured with arrows was sweating condensation water excessively at the outside coils, which is unusual (but it did operate correctly). I would ask the current owner when these Heat Pumps were serviced last. If they have not been serviced in the last 12 months all four need to be serviced now, but the Heat Pump in picture 1 needs service now.

Testing the systems in the cooling mode the supply temperatures were 51-56 degrees (average) which is normal for this type of cooling system. All heating and cooling systems need to be serviced yearly by a qualified professional so they operate efficiently. Refrigerant levels need to be checked and the condenser coils cleaned. A system supplying air even one or two degrees lower after service will greatly reduce your electrical consumption.

7.2   REFRIGERANT LINES FOR AC EQUIPMENT
  Repair or Replace
The refrigerant pipe from the Air Conditioning Unit(s) to where they enter the roof of the building need the insulation replaced for maximum efficiency of the system.

8.  INTERIOR OF THE ENTIRE BUILDING
8.0   FLOORS
  Repair or Replace
There are various cracked floor tiles that need to be replaced at the front entryway, it looks like they cracked because the concrete floor under the tiles cracked, which is common for all concrete floors, especially large ones if there was not sufficient expansion joints in the concrete.

The tiles need to be replaced and a "Slip Sheet" installed under the cracked tiles if there is a minor crack in the concrete floor to prevent the tiles from cracking again. The easiest way to describe a "Slip Sheet" is to say that this membrane isolates the tile, bonding coat, and setting bed from the supporting element. Slip Sheets are commonly asphalt impregnated papers, 15lb. roofing felt, and polyethylene sheeting.

The concrete under the tiles expands and contracts from heat, and cooling which is the primary cause of tiles cracking installed on concrete floors, a Slip Sheet installed under the cracked tiles before they are replaced will prevent them from cracking in the future.

8.1   WALLS, CEILINGS
  Repair or Replace
There are Numerous repairs needed on the sheetrock walls throughout the building, (typical) normal settlement is common and repairs to the walls are needed.

If the walls were cracked all the way to the floor from the ceiling and the foundation was also cracked, it would be a major concern, but I did not see anything unusual besides the fact it looked to me like none of the settlement cracks have been repaired since the building was constructed.

There are a two moisture stains on the ceiling tiles, one in the conference room where the flat roof above it needs to be sealed and water is lying near the roof drain, which could be directly related to the stains, but nothing was leaking today. The roof needs to be repaired above this portion of the building (see roof section of this report).

8.6   SPRINKLER SYSTEM
  Not Tested
The system was inspected in May of 2007, I would have the company noted in the inspection certificate (pictured) reinspect the system when you close escrow.

Abrigo Fire Protection
602.237.2588


Inspect Arizona Companies, Inc.

Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2007 : Licensed To Inspect Arizona Companies, Inc.
Top Table of Contents Bottom